Troubleshooting
Why a Servo Shows a High Torque Alarm at Standstill
Short answer
A high torque alarm at standstill means the enabled axis is drawing real current against a position error, a holding brake, or an external load, and copper loss rises with the square of that current. Check the drive's actual RMS current against the motor's documented continuous standstill rating, then work the causes cheapest first: connectors and feedback, brake sequencing, loop stability and commutation, then cable interference.

On this page
A high torque alarm on an axis that is not commanded to move usually means exactly what it says: the drive is delivering substantial current at zero speed. An enabled position axis develops holding torque against a position error, a still-applied holding brake, gravity or an external load, and winding heat rises with the square of the current. The decisive check is the drive's actual RMS motor current against the motor's documented continuous standstill rating, read from the drive diagnostics rather than guessed from a multimeter on a pulse-width-modulated output. Then work the causes cheapest first: connectors and feedback continuity, brake sequencing, loop stability and commutation, and finally cable interference.
Why zero speed is not zero current #
Zero shaft speed means zero mechanical output power, but an enabled servo at standstill can still carry full current. Torque in a permanent-magnet servo motor is approximately proportional to torque-producing current within the normal operating range, so the drive supplies whatever current the position loop demands to hold the commanded position.
Copper loss in the windings is the heating that matters, and it scales with the square of current. This is a calculated example, not a measured result: if the motor's continuous standstill current is, for example, 3 A and the drive is actually delivering 6 A RMS, the copper loss is (6 A / 3 A) squared, that is four times the continuous heating, even though the shaft is not turning. At 9 A it is nine times. That is why a modest-looking overcurrent can trip a thermal alarm within the allowed overload time, and why raising the torque threshold without finding the demand only lets the heating continue.
Compare like with like: RMS, peak, phase current and torque-producing current are different definitions, and each drive display and each motor rating defines its own. Identify which definition the alarm threshold uses before judging it.
Measure before you adjust anything #
The deciding quantity is actual motor current relative to the motor's permitted continuous standstill current, plus its duration and the thermal conditions. A high torque indication alone is not that measurement, because its meaning depends on the configured source: torque demand, estimated torque, a current threshold, or another status condition in that drive's documentation.
An ordinary multimeter across the drive output is a poor basis for any decision. The output is pulse-width modulated, so the displayed voltage depends on the instrument's measurement method. Use the drive's own current diagnostics, and where you need an independent reading, an instrument specified for drive output waveforms.
Take these from the drive diagnostics and the motor's manufacturer documentation for the exact motor:
- Actual RMS motor current, compared using the same current definition as the rating
- The motor's continuous standstill current and thermal limits from its datasheet
- Peak current capability and the permitted overload duration, from the drive and motor overload documentation and the active settings
- Position error, meaning commanded position minus actual position in matching units, from the drive or controller trace
- Brake state and enable state, trended alongside the current
One safety note: do not unplug motor-power or feedback connectors on an energized axis. Isolate power, follow the drive's documented discharge wait, and secure any load that can move when motor torque or the brake is removed. Capture the drive's status and fault history before resetting or disturbing connections whenever the machine can be left safely in that state, because a restart clears the evidence you need.
The causes, cheapest to check first #
Treat the symptom as one of these; confirm each before assigning a cause.
-
Connector and feedback continuity. An intermittent contact in a power or feedback connector changes contact resistance, feedback continuity, shield contact and the controller's accumulated error all at once, which is why reseating connectors sometimes makes the indication vanish. A continuity test that finds no permanent open or short still leaves intermittent contacts and vibration-sensitive connections unresolved. Confirming check: with the shaft mechanically stationary, trend reported position. A motionless shaft with changing reported position points to the feedback path. Reseat and inspect the connectors under the lockout procedure above, and wiggle-test the cable while watching reported position and current.
-
Holding brake still applied. If the brake remains applied while the position loop tries to correct a small error, the rotor cannot move and the integral action winds up until the drive reaches full current and faults. This happens with no mechanical jam at all. Confirming check: trend commanded position, actual position, torque demand and brake state together. Demand that rises while position error persists and the brake reads applied is this mechanism. Brake state and release current must be wired and sequenced so the controller knows whether the axis is held mechanically or expected to regulate electrically; brake circuits are wired so the brake releases only when the drive commands it, and a brake that never receives release current holds the shaft against every correction the loop makes.
-
Loop instability or commutation trouble. An unstable position or current loop oscillates at standstill, and an incorrect commutation reference can produce large current with little useful torque. Confirming check: record current, position and velocity together. Current that oscillates with audible excitation or vibration indicates instability or feedback disturbance; high current with stable position and no useful holding force points to a commutation or motor-setup fault. Re-verify the commutation alignment by the drive manufacturer's documented procedure before changing loop gains, and check the mechanics (lubrication, guideways, screw, counterbalance) because normal-looking motion does not measure holding force.
-
Cable interference over the documented run length. Shielding defects or a cable run longer than the drive's documented maximum can inject disturbances on the feedback lines, causing apparent position error and elevated current. Confirming check: measure the actual cable length against the drive documentation's limit, inspect shield continuity and the drive-end shield termination, and see whether the fault correlates with a nearby switching load. Route or replace the cable to the documented specification.
-
Drive hardware stressed by past overloads. A drive that has been overloaded may now fail at currents below its rating. Confirming check: with the motor disconnected and every other cause cleared, compare the drive's reported current with an independent measurement under a known light load. Persistent disagreement means the drive itself needs service.
Worked example: is the current the problem? #
Decide with the ratio, not the alarm. Suppose the drive diagnostics show 6 A RMS at standstill and the motor datasheet lists 3 A continuous standstill current for the mounted thermal conditions (these are example inputs, not ratings of any specific motor). The copper loss ratio is (6 / 3) squared = 4, so the windings are heating at four times the continuous rate and the alarm is doing its job: find the demand using the order above.
Suppose instead the diagnostics show 2.5 A RMS against the same 3 A rating, but the torque-high indication still appears. Then the motor is within its continuous capability and the indication is not measuring what you assumed: identify the exact status source and threshold in the drive configuration, and check whether the threshold is set below the normal holding current for this axis. The fix there is a correctly derived threshold, never a lowered one that masks a real overload later.
The decision #
Read the drive's RMS standstill current and divide it by the motor's documented continuous standstill current. Above 1.0, the alarm is real: work causes 1 through 5 in order and fix the demand before touching any limit. At or below 1.0 with the alarm still active, the indication source or threshold is the problem: identify what the drive is actually reporting and set the threshold from the axis's real holding current. Either way, do not unplug connectors live, and never raise the torque limit while the cause is unknown, because copper loss grows with the square of the current you are allowing.
Questions asked
Can I measure servo output current with an ordinary multimeter?
Not reliably. The drive output is pulse-width modulated, so a multimeter's reading depends on its measurement method and how it averages switching waveforms, not on a clean value you can compare with a rating. Use the drive's own current diagnostics for torque-producing and RMS current, or a clamp meter specified for PWM drive output. The same caution applies to voltage across the output terminals.
Why does the alarm appear about once a week and then disappear?
An intermittent pattern points to a condition that comes and goes rather than a permanent fault: a vibration-sensitive contact in a power or feedback connector, marginal shielding on a cable run, a brake that sometimes fails to release, or accumulated position error that only crosses the current limit after certain command sequences. Capture the drive status before resetting anything, because a restart clears the evidence.
Can I just raise the torque limit to stop the alarm?
No. The alarm is telling you the axis is demanding more current than its threshold, and raising the threshold lets sustained winding heating or an unstable loop continue uncorrected. Copper loss rises with the square of current, so a modest overcurrent heats the windings disproportionately. Identify what is demanding the current first; only then adjust the limit if the application genuinely needs more holding torque.
Does zero mechanical output power mean the motor is not heating?
No. At standstill, shaft power is zero because speed is zero, but copper loss in the windings continues as long as current flows. That is why an axis holding position against gravity or a brake can overheat while producing no motion, and why the comparison that matters is actual RMS current against the motor's documented continuous standstill rating and its duration.