Troubleshooting
Why a Vertical Axis Servo Motor Overheats: Counterbalance Loss
Short answer
A vertical-axis servo that heats abnormally and trips only when the axis moves is usually fighting a dead counterbalance, not failing electrically. The sealed nitrogen gas spring that offsets the head's weight leaks down over roughly 5-10 years, and the motor then carries the full weight as continuous current. Confirm it with the belt-disconnected no-load test, check the balance with the screw disengaged, and replace the spring with a matched rating.

On this page
On a vertical axis, a servo motor that runs cool on the bench but overheats and stops the axis under load is usually not a bad motor: it has lost its counterbalance. The gas spring that offsets a Z-axis head's weight is a sealed nitrogen cylinder, it leaks down over roughly 5-10 years, and once its force is gone the motor carries the full head weight through every upward move as near-continuous current. The case behind this article: a 24 VDC, 60 W brushed servo on a small CNC gantry, nameplated 3.5 A and 2800 RPM, whose Z motor, encoder and the metal around them became too hot to touch and stopped the system on any upward move while the other gantry motors stayed cool. The belt-off no-load test, the balance check and the spring replacement below follow that fault from symptom to verified repair.
Read the symptom before blaming the motor #
Write down what was actually observed, because the pattern is the diagnosis. Here: the motor, its encoder and adjacent metal ran hot to the touch during normal work; the heat climbed until any Z move stopped the whole system; after a full cooldown the machine ran again for a while and tripped the same way; the neighboring gantry motors never got warm; and the Z head still moved by hand without noticeable resistance right up to the trips. A servo running near its rating is supposed to run warm. The fault markers are heat that keeps climbing past the temperature of the parts around it, heat confined to one axis, and a drive that stops the axis on current. The free hand movement matters too: a screw, nut or guide seized hard enough to overload a motor is usually stiff enough to feel by hand.
Run the no-load test with the belt off #
This test splits the problem in half, and it comes first because it costs nothing. One caution before starting: a Z head held only by a weak spring is held by gravity alone, and a charged gas spring stores energy with the machine off, so support the head before breaking the drive train; OSHA's control-of-hazardous-energy standard (29 CFR 1910.147) requires stored energy like gravity and charged springs to be restrained before servicing.
- Power the machine down and block or screw-jack the head so it cannot move.
- Disconnect or slacken the belt between the servo motor and the ball screw.
- Restore power and jog the motor up and down through its normal speed range for 15-20 minutes of continuous running.
- Feel the motor housing at intervals and note whether the axis-stop fault reappears.
If the motor now runs cool and the stop never appears, the motor, brushes and drive are doing their job and the fault is in the load behind the belt, which was the result in this case. If the motor still heats with no load, the drivetrain is exonerated and the motor is suspect: work through how to tell if a servo motor is actually faulty before buying parts.
Likely causes, cheapest first #
For a vertical axis that heats only under load, check these in order. Each carries its confirming check, not just a suspicion.
- Belt and drivetrain drag. An over-tight belt, a dry ball nut or a binding carriage raises the torque every move needs. Confirm: with the belt off, rotate the ball screw by hand through the full travel. Binding at one spot convicts the screw, nut or guides, not the counterbalance.
- Lost counterbalance force. The leading suspect when the head moves freely by hand yet the motor bogs and trips going up. Confirm: where the machine design allows, disengage the screw from the head. A balanced head stays where you leave it or sinks very slowly; a dead spring lets the head fall under its own weight.
- Worn brushes. Brushes worn down to the springs can overheat a DC brushed motor, but ordinary wear rarely does, and a clean unloaded run argues against them first. Confirm: pull a brush and check its length against the wear line in the holder, and look for arcing or chipping.
- Encoder or drive fault. A feedback problem usually announces itself as position error or rough motion rather than steady heat. Confirm: if the unloaded motor jogs in steps with current that fluctuates, follow the diagnosis for a servo axis that jogs in steps with fluctuating current instead of chasing the load.
Why a lost counterbalance leads the list #
The counterbalance is the one part of a vertical axis with a service life that ends in exactly this symptom. It is a sealed cylinder charged with nitrogen at the factory, not an air cylinder fed by the shop compressor, and the charge leaks past its seals over roughly 5-10 years. Once the force is gone, every upward move asks the motor for the head's full weight as continuous torque instead of the small unbalanced remainder, and a motor of this class (the case motor is rated 60 W output) has little thermal margin above its continuous duty. The other parts age differently: a dragging screw or guide shows up in the hand-rotation check, while a spring can lose half its force with nothing you can feel. Turning up the shop-air regulator does nothing here; on most machines that regulator feeds tool release and clamping, and the balancer is not on the air system at all. If the axis is being redesigned rather than repaired, the balance and sizing logic for a pneumatic counterbalance on a vertical Z axis carries straight over.
Example: sizing the replacement for a dead 25 lb gas spring #
Inputs, with their sources:
- Original spring rating: 25 lb, the machine's original balancer rating from the case.
- Replacement candidates: 30 lb and 40 lb, the next standard ratings considered in the case.
- Conversion: 1 lb = 4.448 N.
The rule, in words: how far a candidate sits above the original is (candidate - original) / original x 100, and the upward force the motor gains when the spring is fully dead is the original rating converted to newtons.
The arithmetic:
- 30 lb: (30 - 25) / 25 x 100 = 20% over the original.
- 40 lb: (40 - 25) / 25 x 100 = 60% over the original.
- Dead-spring deficit: 25 lb x 4.448 N/lb = 111.2 N of extra upward axial force the screw and motor must carry on every climb.
Result: a 30 lb spring sits 20% above the design balance point and a 40 lb spring 60% above, while a fully dead 25 lb spring adds 111.2 N of axial load. This is a calculated example for these inputs, not a measured result.
Decision: fit a fresh 25 lb spring where one is still made, because it restores the designed balance exactly. Where decay margin is wanted, the 20% step to 30 lb is the defensible choice, as in this case: it adds only 5 lb (22 N) of upward overforce for the motor to resist on the way down, and it compensates years of leakage ahead. The 40 lb spring at 60% over is not a direct substitute: 15 lb (67 N) of permanent overforce drags the motor on every downward move and can let the head creep up when idle. Rating alone does not make a spring fit: length, stroke and end fittings must match the old part, which you verify from the old spring and its datasheet.
Verify the repair under load #
Reconnect the belt, remove the blocking, and run the Z axis through real work. The repair is confirmed when three things hold together: upward moves no longer stop the system, the motor's temperature after a normal session is comparable to the neighboring gantry motors, and the screw-disengaged balance check shows a head that stays where it is left. If the unloaded motor ran clean but the loaded fault survives a new spring, the counterbalance was not the whole story: go back to belt tension and screw drag, then to the drive's current limit, before replacing the motor.
Questions asked
Why does only the vertical axis motor get hot while the other gantry motors stay cool?
Horizontal axes see friction and acceleration loads in short bursts, so their motors cool between moves. A vertical axis works against the head's weight through every second of upward travel, so a lost counterbalance pushes the Z motor toward continuous rated current while its neighbors never approach it. Compare motor temperatures only between axes doing comparable work.
Is some warmth from a servo motor normal?
Yes. A servo working near its rating runs warm as designed, and a housing you can only just keep a hand on is a common field rule of thumb for acceptable. The signs of a fault are heat that keeps climbing past the temperature of nearby metal, heat limited to one axis, and a drive that stops the axis on current. Warmth alone needs no action.
How should I read the date stamped on a counterbalance gas spring?
Treat the stamp as a build date, not a guarantee. The marking in the case behind this article can be read as December 2003 or March 2012, and neither reading decides the outcome by itself: a spring that old is likely low on charge, but a younger one can leak early too. Record the stamp, then judge the spring with the disengaged-screw balance check.
Can a weak counterbalance gas spring be re-gassed instead of replaced?
No. These balancers are sealed, welded cylinders charged with nitrogen at the factory and have no fill valve, and they are never connected to the shop air system, so an air regulator has nothing to do with them and there is no port to top one up. Replacement of the complete spring is the only service path.