Why a Servo Axis Never Reaches Its Commanded Speed

Servo and stepper motion Published 8 min read By AutomateDirectUSA engineering team

Short answer

A servo axis tops out at the lowest of three ceilings: the screw or actuator's documented linear speed limit, the peak a short move can reach through its accel and decel ramps, and the electronic gear ratio that turns command units into encoder counts. Worked example: a 20 mm screw limited to 600 mm/s caps a 3000 rpm motor at 1800 rpm.

On this page
  1. Which of three limits is capping my axis speed?
  2. How fast can my ball screw or actuator turn the motor?
  3. Why does a short move never reach its peak velocity?
  4. How does the electronic gear ratio set how fast my axis moves?
  5. Why does my controller reject a higher velocity command?
  6. What do I check first, and in what order, on a slow servo axis?
  7. Will a bigger servo motor make my axis faster?
  8. Questions asked

A servo axis that runs slow almost never has a weak motor. Its speed sits at the lowest of three ceilings: the linear speed limit of the screw or actuator, the peak a short move can reach inside its accel and decel ramps, and the electronic gear ratio that converts command units into encoder counts. The worked example used throughout is a real configuration: a 20 mm lead screw in an electric cylinder the maker rates to 600 mm/s, a servo motor rated 3000 rpm with a 2^20-count incremental encoder, driven direct. On that axis the reachable ceiling is 1800 rpm, not 3000. Check the three ceilings in the order below and the slow axis names its own cause.

Which of three limits is capping my axis speed? #

Take the lowest of three numbers: the screw's linear limit in rpm, the peak a move of your length reaches through its ramps, and the motor speed your scaled command maps to. On the worked axis the lowest is 1800 rpm, and the screw wins.

A healthy servo follows the command it is given. If the drive's speed monitor shows the axis parked steadily at some speed, the loop is doing its job, and the real question is what that command means mechanically. Each ceiling leaves a different fingerprint: a steady speed below target points at command scaling or the screw limit, a move that takes longer than distance divided by peak speed points at the ramps, and an entry the controller refuses points at its accepted data range. The next three sections quantify each one for the worked axis.

How fast can my ball screw or actuator turn the motor? #

Divide the actuator's documented linear speed limit by the lead and multiply by 60: with the 600 mm/s limit and a 20 mm lead, the screw caps the motor at 600 × 60 ÷ 20 = 1800 rpm, so this motor's 3000 rpm rating is mechanically unreachable.

The inputs are the actuator maker's stated maximum linear speed for this screw and the 20 mm/rev lead; take both from the datasheet of your exact actuator, because the limit belongs to that screw's geometry, including its unsupported length and critical speed, not to servo motors in general. The conversion runs both ways: rpm = linear speed × 60 ÷ lead, and linear speed = rpm × lead ÷ 60. The same conversion sets speed targets on other transmissions, as in correcting rack and pinion speed and torque for a gantry retrofit.

Linear speed Command value (µm/s) Motor rpm at 20 mm lead Verdict on the worked screw
300 mm/s 300,000 900 Comfortably inside the limit
533 mm/s (320 mm in 0.6 s) 533,000 1600 Feasible only with strong ramps
600 mm/s 600,000 1800 The screw's documented maximum
800 mm/s (320 mm in 0.4 s) 800,000 2400 Impossible on this screw
1650 mm/s 1,650,000 4950 Past the motor rating, far past the screw

Why does a short move never reach its peak velocity? #

A move shorter than v² ÷ a never reaches peak speed, because the accel and decel ramps meet as a triangle. At the screw's cap of 0.6 m/s with an illustrative 5 m/s², the threshold is (0.6 m/s)² ÷ 5 m/s² = 0.072 m = 72 mm.

The worked machine needs a 320 mm stroke, so at that accel the profile is a trapezoid: each ramp covers 0.6² ÷ (2 × 5) = 36 mm and takes 0.6 ÷ 5 = 0.12 s, leaving 248 mm of cruise at the cap (0.41 s), for about 0.65 s total against the naive 320 ÷ 600 = 0.53 s. The unit it replaces does the stroke in 0.4 s, which averages 800 mm/s, above the screw's linear limit, so no accel value fixes that. The actuator maker's own claim of 320 mm in 0.6 s needs about 9 m/s²: ramps of 2 × 0.6 ÷ 9 = 0.13 s covering 40 mm, then 280 mm of cruise in 0.47 s. The drive builds this profile itself from its accel and decel settings and triangulates a move too short to reach the commanded speed. An axis's usable accel comes from sizing, which the calculation of servo axis acceleration for torque sizing sets, and raising ramps past that torque is the mechanism behind why a servo faults when acceleration ramps increase.

How does the electronic gear ratio set how fast my axis moves? #

The gear pair defines how many encoder counts one command unit is worth: 1,048,576 counts ÷ 20,000 µm per revolution = 52.4288 on the worked axis. Leave a default 1:1 ratio in place and the controller's command output rate becomes the true ceiling, far below the motor nameplate.

With 1:1 gearing, holding 3000 rpm means 50 rev/s and would demand 50 × 1,048,576 = 52,428,800 command counts per second, more than a pulse-train controller generates, so the axis crawls no matter what velocity number you type. Setting the pair to encoder counts per revolution over command units per revolution (on the worked drive, Pn009 = 1048576 and Pn010 = 20000; your drive's manual names its own pair and its permitted band) returns ordinary command rates at sane values. The worked drive's band runs from 1/1000 to 1000: millimetre units would need 1,048,576 ÷ 20 = 52,428.8, out of band, which is why the command unit becomes the micron and 52.4288 fits. Verify by travel, not by hope: command 10,000 µm at low speed and measure 10.000 mm of motion; a mismatch means the scaling is still wrong. The same counts-per-unit logic is what setting gear ratio for degree moves on a rotary servo axis works out.

Why does my controller reject a higher velocity command? #

A rejection is a data-range check on the command value, not proof the motor hit its ceiling: the worked controller accepted up to 1,650,000 µm/s (1650 mm/s, or 4950 rpm) and reported its data-setting error, code 94, above that, while the screw's real limit sits at 1800 rpm.

The controller validates against motor-side data and knows nothing of your lead or actuator, so an accepted value can still be mechanically impossible: 1,650,000 µm/s commands 1650 mm/s into an actuator capped at 0.6 m/s. Record the boundary, meaning the code, the rejected value and the profile settings, then convert it to rpm and see which device's limit it mirrors. In the worked example the boundary sits near the motor's own maximum, which confirms the screw is the binding limit. Clamp the velocity in the controller or PLC at the screw's documented figure, 600,000 µm/s on this axis, so no program or operator entry can ask for more than the actuator can survive.

What do I check first, and in what order, on a slow servo axis? #

Work from cheapest to most expensive: capture the command trace, convert it to rpm against the screw's limit, run the motor uncoupled, verify travel per command unit, time the move, then read the rejection boundary. Most slow axes are solved at step two or four.

  1. Capture commanded velocity, actual motor speed from the drive monitor, travel, move time and any alarm in one record, before changing anything.
  2. Convert the command to rpm (linear speed × 60 ÷ lead) and set it against the screw's datasheet limit and the motor's rating; the lower of the two governs the axis.
  3. Run the motor uncoupled from the screw, after isolating and locking out the drive per the machine's procedure and letting stored energy discharge before breaking the coupling. Still slow uncoupled means scaling or profile; fast uncoupled points at the mechanics: nut drag, lubrication, misalignment or the load itself.
  4. Verify travel per command unit with a short measured move; a mismatch is the gear pair, not speed tuning.
  5. Time the move against distance ÷ peak speed; if the time is longer, the ramps dominate, and the triangle threshold v² ÷ a says which moves can never get there.
  6. Read the rejection boundary if higher values alarm, convert it to rpm, and clamp the axis's software velocity limit at the screw's documented figure.
  7. Leave the regenerative resistor out of the speed question: it absorbs braking energy, not top speed, and only enters this diagnosis when deceleration trips an overvoltage alarm, as why a motor-side braking resistor works on a PM servo explains.

Will a bigger servo motor make my axis faster? #

No. On a fixed lead, linear speed is rpm × lead, and larger frames rarely spin faster, because they are built for torque. The worked axis's screw stops the motor at 1800 rpm against a 3000 rpm rating, so speed headroom the screw cannot use already exists.

The decision splits three ways. If the screw limits, as here, the fix is an actuator with a higher documented linear-speed limit, usually a longer lead, and then you recheck the rpm demand, thrust and torque at the new speed; a larger motor only increases the damage a jam does to that screw. If the motor limits, meaning a short lead chasing a fast stroke, add a transmission step so the motor works in its fast band and redo the linear conversion. If the ramps limit short moves, raise accel only within the accel torque the motor and drive actually have. For the worked axis: clamp the command at 600,000 µm/s, expect roughly 0.6 to 0.65 s for the 320 mm stroke depending on the accel the drive can deliver, treat 0.4 s as out of reach for this actuator, and select a higher-speed actuator only if the cycle genuinely requires it.

Questions asked

Do I need to recompute the electronic gear ratio after replacing the servo motor or encoder?

Yes. The numerator is the encoder's counts per revolution, so a different encoder resolution changes the ratio even if the mechanics are untouched. Recompute counts per revolution against travel per revolution, re-enter the pair, then re-verify with a measured move: command a known distance, measure the travel, and confirm they match before running production.

How much headroom should I leave between my working speed and the motor's maximum rpm?

Treat the rated speed, not the maximum, as the continuous working ceiling, and take both figures from your motor's datasheet. Torque falls as speed climbs toward the maximum, and the control loop needs spare speed to correct errors during accel and load changes. Size the accel torque at the speed where the ramp actually happens, not at zero rpm.

How do I check my scaling from the drive's speed monitor alone?

Read the actual motor speed in rpm while the axis holds a steady command, multiply by the lead and divide by 60 to get the expected linear speed: 900 rpm on a 20 mm lead means 300 mm/s. If the measured travel rate disagrees with that product, the gear ratio or command units are wrong; if it agrees, the command value itself is simply low.

If my command unit is one micron, can I position to one micron?

No. The gear ratio sets command resolution, not mechanical accuracy. A micron-sized command increment does not make the screw, nut, coupling or frame accurate or repeatable to a micron; achievable accuracy comes from the mechanics, including backlash, compliance, thermal growth and the feedback device. Size the command unit to keep the gear ratio legal, then judge accuracy by measured moves.

Keep reading

  • Explainer

    Servo Positioning Resolution Versus Stepper Step Angle Explained

    A 0.018° move needs 360 ÷ 0.018 = 20,000 usable feedback counts per revolution, which come from the encoder and the drive's decoding and scaling, not from the servo label. Matching 3,000 command pulses per revolution on a stepper and a servo only matches command scaling; short-time overload capacity and high-speed performance still differ.

    Servo and stepper motion

  • How-to

    Setting Up Servo Electronic Gearing With Registration Correction

    Gear the folder servo to the web encoder with one fixed electronic gear ratio and apply registration error as a bounded phase trim ramped across the 100 to 200 ms between corrections. At 150 m/min a 0.1 mm tolerance is 40 microseconds of web travel — about eight 0.0127 mm increments — so doubling or halving a pulse train for six pulses trips following error, while a ramped trim changes speed by 0.04 percent.

    Servo and stepper motion

  • Troubleshooting

    Why an EtherCAT CSP Stepper Axis Enables but Does Not Move

    Holding torque on Servo On proves only that the power stage energizes the windings. In cyclic synchronous position mode the axis moves only when the drive accepts each new 0x607A target and no internal limit refuses it, so check Statusword bit 11 first, then the drive's speed, current and software position limits, then the position unit scaling between controller and drive.

    Servo and stepper motion