Troubleshooting
Why a Servo Gripper Trips Overload at the Closed Jaw Position
Short answer
The trip is thermal, not logical: when the jaws stop on the part before the commanded close position, the unclosed position error keeps the servo drawing stall current, and the overload model accumulates until it trips. End the closing move on detected contact - motion stopped plus a torque or current threshold - and transfer the axis to a controller-supported limited-force or soft-absorber hold; do not raise the trip setting.

On this page
- What the overload alarm actually measures
- Why a fixed close position guarantees the trip across a size run
- Worked example: how much faster the hold fills the accumulator
- Likely causes, cheapest to check first
- End the closing move on detected contact
- What holds the grip after contact
- Adjustments that hide the symptom
- Verify on the machine, then decide
- Questions asked
A servo gripper that trips its overload error at the closed position is not haunted by a bad drive. The jaws stopped on the part before the commanded close position was reached, the unclosed position error kept the motor drawing stall-level current for the whole grip dwell, and the drive's thermal overload model accumulated that current until it tripped. A 1 kW motor pushing through a 1:20 reduction, as in the reported installation, turns even a small unclosed error into a large sustained torque demand. The alarm is the protection working. The fix is to end the closing move on detected contact - motion stopped plus a torque or current threshold - and transfer the axis to a controller-supported limited-force or soft-absorber hold, not to raise the trip setting or command extra overtravel.
What the overload alarm actually measures #
A servo drive's overload decision is a thermal model. It integrates motor current against a current-time characteristic documented for that motor and drive family and trips when accumulated load crosses the curve. Current stands in for torque, so a stalled axis pushing its torque clamp looks to the model exactly like an axis doing hard work; the model cannot see that the jaws stopped.
While the jaws travel free, a close draws current for acceleration and friction only. The moment the jaws meet the part with commanded position still ahead, the position regulator raises its demand to close an error it can never close, and current sits at that demand for as long as the grip must last. An axis held at or below the documented continuous rating never crosses the curve; the trip needs current above it, sustained long enough. Overload alarms that build up this way on main axes follow the same accumulator arithmetic, covered in why a servo drive trips an overload alarm mid cycle.
Why a fixed close position guarantees the trip across a size run #
The reported gripper handles parts with a deviation of -3 to +3 mm, a 6 mm total span. A closing coordinate taught on the smallest part puts the jaws exactly where the smallest part is gripped. On the largest part the jaws stop 6 mm short of that coordinate. The command is a position, so the regulator still owes travel it can never collect from a rigid part.
Position limits do not intervene: commanded and actual both sit inside every configured open and close limit, which is why limit settings alone never catch this. The dwell does the rest. A grip that must hold for seconds or minutes gives the accumulator all the time it needs, so the trip lands mid-grip at the closed position, which is exactly where this alarm is reported.
Worked example: how much faster the hold fills the accumulator #
Take the reported installation with illustrative hold figures. The close coordinate taught on the smallest part leaves up to 6 mm of unclosed travel against the largest, so the loop holds its torque clamp for the whole dwell. Assume the clamp sits at 1.5 times the motor's continuous current - an example value, not a rating; read the real clamp and the continuous figure from the documentation for the installed motor and drive.
Heating scales with current squared: 1.5² = 2.25, so this hold fills the overload accumulator 2.25 times faster than a hold at continuous current and reaches the trip level in 1 / 2.25 ≈ 0.44 of the time the axis could hold at continuous current, less than half. Easing the demand to 1.1 times continuous gives 1.1² = 1.21, which stretches the same window to 1 / 1.21 ≈ 0.83 of the continuous-safe time. The demand sets the clock, and only removing the demand at contact stops the clock.
Likely causes, cheapest to check first #
Work down this order; each item names the cheap check and what confirms it.
- Close position taught past the part. Command a close on the largest permitted part and read commanded against actual on the position monitor. Confirmed when actual stops while commanded sits one part-span further, and the error at the stop equals that span.
- No contact exit in the closing logic. Read the closing step of the program. Confirmed when the step waits on in-position or a timer, with no torque, current or remaining-distance condition anywhere in it.
- Mechanical drag loading the axis before any part arrives. Close at production speed with no part and watch the current monitor. Confirmed when the empty close alone draws near or above the drive's continuous level. The drag lives in the transmission, and if it traces to the joint between the motor shaft and the reduction stage, fitting a new flexible shaft coupling is the repair that removes it.
- A contact spike misread as this fault. Trend current through one full close at the installation's reported 510 mm/s closing speed, then at half speed. Confirmed when the trace shows a short spike with no plateau afterwards: that is a transient, treated with closing speed and the acceleration-time setting, while a flat plateau from contact to trip is the unclosed-position hold described here.
- Overload or limit parameters already raised to mask the symptom. Compare the drive's overload and travel-limit settings against the motor and drive documentation delivered with the machine. Confirmed when any setting sits above the documented curve; restore the documented values and fix the demand instead.
End the closing move on detected contact #
The close must stop being a pure position move the instant the jaws touch. Supervise it with three conditions evaluated together: the axis is commanded closing, remaining travel has fallen to about zero, and torque or current has crossed a validated grip threshold. All three together reject an acceleration spike and identify a jaw that has physically stopped.
On a controller programmed in AS, the robot language Kawasaki documents for these controllers, the manual documents the monitor command I2PG for reading motor torque as current, nested inside a WHILE DO supervision structure - that is the pattern for this check. The remaining-distance function appears as DISTANCE in one reference and DIST in another, so confirm the spelling and external-axis support in the reference for the installed controller before writing production logic. The toolset reported for this duty also includes DEXT and HSENSE, usually mapped through I/O; treat both as leads to verify against the installed controller's command reference. Where the state has to travel through software signals, that controller family documents numbered internal signals, 2000 to 2256, in its internal I/O setup documentation.
Set the threshold between two measured points: above the highest current an empty close reaches at production speed, below the continuous rating documented for the motor and drive. The measured gap between them is the usable window; no gap means the mechanics or the load path need work first. The same three-part recipe - command a move, watch remaining travel, stop on a torque limit - is what homing a servo axis to a hard stop with a torque limit does against a hard stop, and it transfers to a gripper unchanged.
What holds the grip after contact #
Once contact is confirmed, the axis needs a documented holding behavior, not open-loop silence. Three choices, in the order most cells should try them:
- Torque- or current-limited hold. The drive leaves normal position motion and clamps torque at the validated grip level. The part stays squeezed, the clamp sits at or below the continuous rating, and the accumulator stops filling. Right choice when the grip dwell fits inside the documented continuous limits.
- Compliance in the axis. The controller function reported for this duty is the soft absorber applied to the gripper axis: the servo stays under control but yields over a limited displacement, absorbing the part span without an open position error. Its permitted displacement and load come from the controller documentation; read them before enabling, because compliance set too soft lets grip force fall away on the largest part.
- External mechanical hold. A spring-over-centre linkage or a roller latch captures the grip mechanically so no motor current is needed. Confirm the mechanism takes the load before servo force is removed, or the part releases mid-cycle.
The decision: short dwell with measured hold current at or below the continuous rating, use the torque-limited hold. Part span that must be absorbed inside the axis, use the compliance function within its documented displacement. Long dwell or a tight thermal budget, hold the grip mechanically and let the servo rest at zero demand. Whichever holds the grip, prove on the bench that a servo drop or power loss cannot open the jaws and release the part while the cell runs.
Adjustments that hide the symptom #
- Raising the overload setting. The curve protects the windings; a raised setting only lets the hold cook the motor longer, and it stays legitimate only inside the current-time limits documented for the motor and drive.
- Commanding extra travel past the part. Overtravel deepens the unclosed error, so the loop pushes harder against the same wall and the accumulator fills faster, not slower.
- Leaning on open and close position limits. Limits bound coordinates; they see nothing of force or of time spent above the continuous rating, and this trip is made of exactly those two.
- Cutting closing speed alone. Lower speed trims the contact spike but leaves the sustained hold demand untouched, so the trip moves later into the dwell and still arrives.
- Switching the servo off at contact without a hold plan. Grip force then rests on transmission friction, a brake if the axis has one, or back-driving, which is a part-release risk rather than a fix.
Verify on the machine, then decide #
Record from the installed documentation before any change: the motor's continuous and intermittent current limits, the drive's overload characteristic, the permitted load for the gripper axis, and the transmission limits. Read the controller's displayed current units rather than assuming amperes or a percentage. Trend commanded position, actual position, current and the overload indication through one representative close-and-release cycle, then repeat on the smallest and largest permitted parts.
The reported installation closed at 510 mm/s with an acceleration-time setting of 0.1 in the units its controller displays; keep that setting as displayed during trials, and drop closing speed first when comparing contact spikes against the production baseline. Then decide from the trend. A flat current plateau from contact to trip with the error equal to the part span: apply the contact-exit close and a documented hold. An empty close already near the continuous level: repair the mechanics before touching logic. A single contact spike with no plateau: treat closing speed and acceleration time and leave the hold logic alone.
Questions asked
Does a higher reduction ratio make the overload trip better or worse?
A reduction multiplies jaw force for the same motor current, so a 1:20 stage reaches grip force with modest motor torque, which is why the axis can sit at high current while the jaws barely move. Changing the ratio changes the force available, not the unclosed position demand behind the trip, so the contact-exit fix applies at any ratio.
How do I tell a contact-hold trip from a one-off impact trip?
Watch the current trend through the close. An impact is a short burst at the instant the jaws meet the part that falls away again; a contact hold steps up at contact and stays flat until the trip. The position display separates them too: only the hold case keeps commanded position ahead of actual while the axis sits still.
What happens if I just switch the servo off at contact?
Without a documented hold mode the grip then rests on transmission friction, a brake if the axis has one, or back-driving, and grip force can decay as components heat or settle. Use servo-off only together with a mechanical hold proven to capture the load before servo force is removed, so the part cannot shift or drop mid-cycle.
Can the grip threshold be set as a fraction of maximum current?
Anchor it to two measured points instead: the highest current an empty close reaches at production speed, and the continuous rating documented for the installed motor and drive. The threshold lives between them, and the size of that measured gap tells you whether a valid window exists at all. Work in the units the controller displays, whatever they are.