Troubleshooting
Why a servo spindle ignores a 0-10V analog command
Short answer
A 0-10 V reading at the drive proves the command arrived, not that the drive is using it. Before chasing wiring, confirm the drive is in Velocity mode with the external analog input selected as its speed reference, that enable and direction permission are asserted, and that the source's 0 V is tied to the drive COM. If a 9 V battery through a 1 kΩ resistor also fails to turn the spindle, the fault is in the drive's configuration, and step and direction control is the proven fallback.

On this page
A servo spindle that jogs perfectly from the drive's own panel, holds its shaft the moment the controller enables it, and shows the commanded voltage on both the multimeter and the drive's status display — yet never turns — is not missing a signal. It is missing one of the states that turn a received voltage into motion: Velocity mode, the external analog input selected as the speed source, enable and direction permission, a shared 0 V reference, or a scaling that maps volts to rpm. This article walks those in cost order, splits drive from interface with a battery test, and gives the proven fallback. In the reported 1.8 kW case it follows, the drive never did follow the analog command, and step and direction was the confirmed fix.
What the readings already prove #
Separate what you observed from what you concluded. Four readings were taken in the reported case, and each one closes a branch:
- The motor jogs from the drive's local panel. Drive, motor and power stage can produce motion. Stop suspecting them.
- The shaft is energized and holds when the controller is enabled. The drive is in an enabled, torque-producing state. That is necessary for running but proves nothing about the speed path.
- The command voltage at the drive terminals scales with the speed called for. The controller and its interface delivered a usable signal.
- The drive's own analog-input display matches the multimeter. The drive senses the correct magnitude — which also makes a missing 0 V reference unlikely, because a floating source usually reads wrong or drifts.
None of this proves the drive is in Velocity mode, that the analog input is the selected speed reference, that a direction input is permitting rotation, or that the scaling parameters turn that voltage into a nonzero speed. Those are configuration states, and that is where this fault hides.
The conditions behind a working analog speed command #
Six things must all be true at once:
- Velocity mode selected. These drives offer Position, Velocity and Torque modes, and only Velocity turns a voltage into a speed. If a parameter or a digital input chooses the mode, verify the state that is actually present, not the one you intended.
- The external analog input selected as the speed source. A drive that accepts several references — analog, an internal source, a fieldbus — acts only on the one its configuration points to; the same selection rule is behind why servo drives ignore Modbus speed commands but follow analog.
- Enable asserted the way the drive expects. A held shaft shows the power stage is live, but some drives separate servo-on from run permission, so read the input status the drive itself reports, not the relay state at the interface.
- Direction permitted. A unipolar command carries magnitude only, so the separate CW or CCW input must sit in the state the drive expects while the command is present.
- A shared reference. An interface that builds its command from an isolated internal supply floats until its 0 V terminal is wired to the drive's analog COM.
- Scaling that maps volts to rpm. Offset, gain and linearity all sit between the terminal and the speed loop. An offset equal to the command, or a zero gain, displays a perfect voltage and commands a perfect standstill.
For a concrete picture of what to hunt for: the SureServo documentation lists the operation-mode selection as P1-40 and the analog full-scale velocity command range as P1-55. Your drive will number its own equivalents differently — take every name, range and default from the manual for your exact drive, never from another family's.
Checks in order, cheapest first #
Work top to bottom; each check either closes its branch or hands you to the next one.
- Re-confirm the local jog. It is the baseline for everything after. Note which drive state permits jogging, because local jog often asserts enable internally — that difference is itself a clue.
- Read the drive's fault display while enabled with the command applied. A standing alarm that does not drop the enabled state costs nothing to find and explains everything.
- Meter the analog pair at the drive terminals while calling for three different speeds. The voltage should step in proportion. If it tracks, the controller side is cleared; if it does not, the fault is upstream in the controller configuration or wiring and the rest of this list can wait.
- Bond the interface's analog 0 V to the drive's analog COM. With power off, verify continuity between the two terminals. The matching displays make a missing reference unlikely, but this is one wire and one minute, and it deletes a whole branch.
- Read mode and source off the drive, not the plan. Velocity mode, analog source. Where a digital input selects the mode, watch the drive's own input indicator while the machine tries to run — and check the direction-limit inputs too, because a drive whose limit input sits open refuses to run in that direction even with enable and a perfect command.
- Check what the relays actually do to the drive. Meter the enable and direction contacts at the drive terminals. Inverted logic — the drive waiting for a closed contact while the interface opens it — produces exactly this symptom and costs nothing to find.
- Walk the analog scaling parameters. Offset, gain, linearity, polarity — values from your drive's manual only. A wrong entry here passes every voltage test and still commands zero speed.
- Run the battery test below. It splits the remaining fault space in two.
Proving the drive side with a 9 V battery and a 1 kΩ resistor #
The inputs #
- Command source: a 9 V dry-cell battery — the test proposed in the reported case, comfortably inside the drive's input range.
- Series resistor: 1 kΩ, from the same case, to bound the current into the input while the leads are handled.
- Input range: 0 to 10 V full scale, taken from the drive manual's analog input specification.
- Full-scale speed: whatever the drive's full-scale velocity parameter maps to the full-scale voltage — read it off the drive before starting.
The rule in words #
The resistor limits the current the battery can deliver; the input's impedance is many times higher than 1 kΩ, so essentially the full battery voltage still appears at the terminal. The commanded speed is the applied voltage divided by the full-scale voltage, multiplied by the configured full-scale speed. Disconnect the controller's analog output first so the two sources never share the input, and observe polarity.
The arithmetic #
- Worst-case current, as if the input were a short: I = V / R = 9 V / 1000 Ω = 0.009 A = 9 mA. Nothing is endangered.
- Commanded fraction: 9 V / 10 V = 0.90.
- Expected speed: 0.90 × the full-scale speed you read off the drive. If full scale is the spindle's top speed, expect nine tenths of it on the drive's speed display.
These are calculated values for the inputs above, not measurements — the measurement is what the drive's speed display and the shaft do next.
The decision #
With the drive enabled and the direction input closed exactly as in normal running, apply the battery:
- The spindle turns at about nine tenths of full scale: the drive's analog path is healthy. The fault is in the controller interface — return to checks 3, 4 and 6 and repair the reference or the relay logic.
- The spindle stays stopped: the fault is inside the drive's configuration — mode, source, enable logic or scaling — or the drive itself. Leave the interface alone until the drive follows the battery; nothing you fix upstream can help.
One safety note: if the test succeeds the shaft spins at once, so clear the spindle, close the guard, and run this as a commissioning step under the machine's risk assessment (the ISO 12100 process).
The step and direction fallback #
If the drive still refuses the battery after checks 5 through 7 have been walked against its own manual, stop spending evenings on the analog path. One pass through the parameter list is worth the effort; a fourth rereading is not. Put the drive in Position mode and command it with step and direction pulses. That is exactly what resolved the reported case: the same drive and motor that ignored a perfect analog voltage ran as a spindle on pulse trains, configured from the drive's keypad.
- The drive still closes its position and speed loops on the motor's encoder after the switch; what that means on the machine is covered in when a step and direction servo drive is closed loop.
- The controller must send the pulse frequency that matches the rpm you want; the arithmetic is in calculating step and direction servo pulse scaling.
- The relay scheme simplifies: the enable relay typically stays, and the CW and CCW relay logic gives way to the level of the direction signal.
If you are specifying a replacement drive rather than rescuing this one, the selection questions live in finding a servo drive that accepts a 10V analog command.
The acceptance test before you call it fixed #
A voltage that agrees on two meters is not a repair. Sign off only when all four of these pass on the machine:
- Zero command, enable on: the spindle stays stopped with the shaft held.
- Rising command: speed increases in proportion (analog) or tracks the pulse rate (step and direction).
- Enable removed: the drive drops to its configured stop state — free shaft or brake, whichever its stop-method setting defines.
- Each direction: produces the intended rotation, verified against the tool, not assumed.
The reported case passed exactly this way on step and direction. If your analog path passes instead, keep it — and put the battery-test result in the machine's maintenance record so the next person starts one branch later.
Questions asked
Can one 0-10 V command run the spindle in both directions?
No. With a unipolar command the direction has to come from the separate CW and CCW inputs, not from the voltage. If the drive supports a bipolar -10 V to +10 V reference instead, the sign of the voltage sets the direction and its magnitude sets the speed, so every reversal drives the command through zero — convenient for retrofits of older analog servos, but one more thing to tune.
Is switching the spindle to step and direction a downgrade?
No. The loops the drive closes on the motor's own encoder are untouched, so speed regulation and stiffness stay; only the command format changes. The new limit to check is the controller's maximum pulse frequency: multiply the drive's pulse count per revolution by the top speed in revolutions per second, and confirm the product stays inside that maximum before you rewire anything.
The drive has no setup software. Can I still fix this?
Yes. Mode, source selection and the analog scaling group are ordinary parameters, editable from the drive's front panel, and the reported case was configured entirely that way. What you cannot work without is the manual for your exact drive: parameter meanings, ranges and defaults must come from it, so obtain that document before spending more evenings on the keypad.
Should I bond the interface 0 V to the drive COM if the display already reads correctly?
Yes. The matching readings only make a missing reference unlikely, not impossible. Wire it anyway: one conductor and one minute, and it removes an entire branch of the diagnosis. If the bond was already there you have lost nothing; if it was missing, you have just found the fault.