Why an old stepper glitches on MPG but jogs: check before replacing

Servo and stepper motion Published 7 min read By AutomateDirectUSA engineering team

Short answer

Keep the motors until the switches are read: a stepper that jogs cleanly but glitches on the MPG has a command-path or setting fault, not a dead winding. A commanded 1 in that travels 0.25 in or 0.5 in means the driver is on quarter or half step while the controller still counts full steps. Fix scaling, current and the handwheel multiplier first; replace a motor only when the checks condemn one.

On this page
  1. What a working jog rules out
  2. The distance test comes first
  3. Why the handwheel glitches when jog does not
  4. Set the current before you judge the torque
  5. The checks in order
  6. Keep or replace: the decision
  7. Questions asked

Keep the 1999 motors until you have read two rows of DIP switches. Three steppers that jog smoothly with the slides disconnected have already proved that the motor, its driver and the wiring can execute commands; a glitch that appears only on the handwheel — the manual pulse generator, or MPG — lives in that command path, not in the iron. Run one distance test before spending anything: a commanded 1 in that travels 0.25 in or 0.5 in is the signature of a driver set to quarter or half step while the controller still counts full steps, and a driver current set below the nameplate 1.2 A explains a gantry that will not budge. Replace a motor only when the checks below condemn one.

What a working jog rules out #

Jog and MPG share the same motors, drivers, power supply and step-and-direction lines. They differ only in where the pulses are born: jog pulses come from the controller at a fixed feed with ramped acceleration; MPG pulses come from the handwheel's encoder, multiplied by a scale factor you select. So when an axis turns smoothly in jog and misbehaves by handwheel, the fault sits in pulse generation or scaling — a shorted winding or a demagnetized rotor misbehaves in every mode, at every speed.

The confirming check costs one minute: with the slides still disconnected, run the same axis in both modes at a comparable low rate and watch the shaft. Smooth in jog and erratic by handwheel convicts the MPG path. Erratic in both moves the investigation to current, wiring and the driver.

The distance test comes first #

This is the cheapest decisive test, and it separates a scaling fault from lost steps. Reconnect one axis, clamp a dial indicator to the machine, and jog a known 1.000 in at a slow feed. Divide the measured travel by the commanded travel:

  • A repeatable 0.50 means the driver executes half steps while the controller's steps per inch assume full steps.
  • A repeatable 0.25 means quarter steps against full-step scaling.
  • A repeatable 2.00 or 4.00 is the mirror image: the driver is on full step while the controller assumes microsteps.
  • A random, non-repeatable error is lost steps — look at current, acceleration and pulse rate, not scaling.

The ratios are pure arithmetic and independent of the screw. Take a 1.8 degree motor, which is 200 full steps per revolution, and for the example a screw that turns five times per inch. Full-step scaling is 200 x 5 = 1000 steps per inch. Now put the driver's DIP switches on quarter step: each pulse advances the shaft 1.8 degrees divided by 4, or 0.45 degrees.

Command the distance and the controller emits 1000 pulses; the shaft turns 1000 x 0.45 degrees = 450 degrees = 1.25 revolutions; at five revolutions per inch the axis travels 1.25 divided by 5 = 0.250 in. Measured over commanded is 0.250 over 1.000, a ratio of one quarter. Half step gives the same arithmetic with 0.9 degrees per pulse: 900 degrees = 2.5 revolutions = 0.500 in. This is a calculated example for those inputs, not a measurement of your machine — your step angle and screw lead set the absolute numbers, but the ratios hold for any lead.

Either fix works and only one is needed: put the driver back on full step, or tell the controller the truth with 200 x 4 x 5 = 4000 steps per inch, then repeat the jog and measure the same distance back. A repeatable ratio is always a scaling fault, the same family as an axis that travels 1.25 times the commanded distance.

Why the handwheel glitches when jog does not #

Three causes, cheapest first.

  1. The MPG multiplier is too coarse. Each detent commands a bundle of steps; with a large multiplier selected, one click jumps the axis and fine control vanishes. Set the multiplier to its smallest value, turn exactly ten detents, and check the travel against ten times the per-detent distance. A microstep mismatch also shows up here as coarse control, so correct the scaling before judging the multiplier.
  2. The pulse rate runs past a limit. A fast spin multiplies detents per second by steps per detent, and the driver or the controller's MPG input can saturate — the axis stutters or stalls mid-turn. Confirm by turning slowly: smooth slow and glitchy fast is a rate limit, not a motor. Lower the multiplier or the microstep count; the trade-off is covered in the stepper drive pulse frequency limit versus microstep demand.
  3. The handwheel's wiring or connector. A loose MPG plug or swapped quadrature lines give erratic counts and direction bursts. Step it detent by detent and watch that each click moves the intended axis the intended way.

Set the current before you judge the torque #

The nameplate's 6 V is the voltage across one winding at rated current — a property of the copper, not the supply the driver wants. A chopper driver feeds a higher bus and switches it to hold whatever current its switches select, so the switches, not the nameplate voltage, decide the torque you get.

Read the current DIP bank on each of the three drivers and set it to the motor's 1.2 A. First match the convention, then the number: driver tables state whether their settings are peak or RMS, and the two differ by the square root of two, so 1.2 A peak is 0.85 A RMS while 1.2 A RMS is 1.7 A peak. A driver left at a default current below nameplate produces exactly the reported symptom: a motor that spins freely unloaded and cannot move a gantry. After ten minutes at the correct setting the motor should run warm to hot; a stone-cold motor is being starved. And microstepping will not rescue it — each fine step commands only a fraction of a full step's torque, so resolution is not strength.

The checks in order #

Every step is free; do them in this order and change one setting at a time.

  1. Record both DIP banks — microstep selection and current — on all three drivers before touching anything, so you can return to a known state.
  2. Run the distance test with a dial indicator and compute the ratio; an exact one-half or one-quarter takes you straight to the microstep and scaling fix.
  3. Set each driver's current to the nameplate with the convention matched, then confirm the motor warms up in normal use.
  4. Set the MPG multiplier to minimum, count ten detents against measured travel, and repeat after any scaling change.
  5. Spin the handwheel slowly, then fast; a stall that appears only at speed is the pulse-rate limit.
  6. Swap the motor cables between two axes. If the misbehavior follows the motor, that motor or its cable is condemned; if it stays with the channel, the driver, the wiring run or the scaling is at fault.
  7. Reconnect the slides and test one axis at a time at a low feed with the e-stop in hand. For the mechanical check, hand-crank each screw through its travel with the drive power locked out — your site's lockout procedure, in the US under the hazardous-energy standard 29 CFR 1910.147 — because a binding gib or coupler stalls a healthy motor exactly like a weak one.
  8. Only now buy a replacement, sized from the axis as in sizing stepper motors for a CNC mill, not from the old nameplate.

Keep or replace: the decision #

What you observed What it means Decision
Travel off by an exact one-half or one-quarter ratio, smooth unloaded Driver microsteps do not match the controller's steps per inch Keep the motors; fix the switches or the scaling
Distances correct by jog, glitches only by handwheel MPG multiplier, pulse rate or handwheel wiring Keep the motors; fix the MPG path
One axis erratic in both modes, fault follows the motor in the swap test That motor or its cable Replace that one motor, sized from the axis
Smooth unloaded, stalls loaded at nameplate current with free screws Motors too weak for the axis as built Replace the set, sized from the axis
All three axes show the same symptom Shared configuration, not three coincidental failures Fix the shared setting; keep the motors

Age alone condemns nothing here. A motor that holds, turns smoothly and travels to ratio is doing its job, whatever the date code says.

Questions asked

What do the voltage and current on the motor nameplate actually mean?

They describe one winding at rated current: 6 V across it while 1.2 A flows, which by Ohm's law implies a winding resistance near 5 ohms. That is why the 6 V is not the supply you connect. A chopper driver runs from a higher bus, commonly 24 V to 48 V, and switches it on and off to hold the current you set, so the current switches govern torque and the nameplate voltage does not.

How do I convert my steps per inch when I change the microstep setting?

Multiply the full-step figure by the microstep count: 2 for half step, 4 for quarter step, 8 for eighth step. The example axis in this article goes from 1000 steps per inch at full step to 4000 at quarter step. Recheck the MPG multiplier after the change as well, because handwheel travel scales with the same factor and a stale multiplier brings the glitch straight back.

Do 1999-vintage stepper motors wear out from age alone?

Not from sitting in a dry cabinet. The rotor magnets and stator laminations do not age meaningfully; what fails is mechanical and connective — bearings that feel rough or growl, cracked joints where the leads meet the windings, and heat damage from years above rated current. A motor that turns smoothly unloaded, holds when energized and travels to ratio has told you more than the date code ever could; replace on evidence, not on the year.

Should I replace all three motors if one fails the checks?

No. The swap test condemns one motor at a time, so replace the one that failed and keep the healthy pair running. Replacing the full set is right only when all three stall under load at nameplate current with the screws free by hand — that pattern says the motors are undersized for the machine as configured, and the new set should be sized from the axis torque, not from the old ratings.

Keep reading

  • Troubleshooting

    Stepper Axis Travels 1.25 Times the Commanded Distance

    A constant ratio of 1.25 between commanded and actual travel is a pulse-to-unit scaling error, not a velocity-profile effect: a completed move's distance depends only on the pulse count sent and the pulses-to-distance conversion. Measure R = actual travel / commanded travel at each boundary — command entry, pulse output, driver microstep or electronic gear, gearbox and screw lead — and correct the one setting where R first leaves 1.00. Never hide the error with a compensating multiplier.

    Servo and stepper motion

  • Troubleshooting

    Why an EtherCAT CSP Stepper Axis Enables but Does Not Move

    Holding torque on Servo On proves only that the power stage energizes the windings. In cyclic synchronous position mode the axis moves only when the drive accepts each new 0x607A target and no internal limit refuses it, so check Statusword bit 11 first, then the drive's speed, current and software position limits, then the position unit scaling between controller and drive.

    Servo and stepper motion

  • Explainer

    Servo Positioning Resolution Versus Stepper Step Angle Explained

    A 0.018° move needs 360 ÷ 0.018 = 20,000 usable feedback counts per revolution, which come from the encoder and the drive's decoding and scaling, not from the servo label. Matching 3,000 command pulses per revolution on a stepper and a servo only matches command scaling; short-time overload capacity and high-speed performance still differ.

    Servo and stepper motion