Linear Actuator Potentiometer Feedback for 13 Positions

Linear motion, bearings and guides Published 6 min read By AutomateDirectUSA engineering team

Short answer

Wire the actuator's feedback potentiometer as a voltage divider — 10 V across the outer leads, the wiper to a 0–10 V analog input — and the PLC alone can hold 13 repeatable positions. Two-point calibration with a count deadband is enough; add a drive only when the actuator coasts past its target.

On this page
  1. What the potentiometer tells you
  2. Wiring the pot into the analog input
  3. Calibrate two points, then compute the 13 targets
  4. Worked example: 13 positions on a 100 mm stroke with a 14-bit input
  5. No drive, speed zones, or a drive: the decision
  6. Keeping the reading stable
  7. Questions asked

A linear actuator with a built-in feedback potentiometer is already a position sensor: treat the pot as a voltage divider and your PLC can hold 13 discrete positions with nothing but one analog input and two discrete outputs. Wire 10 V across the pot's outer leads, read the wiper as a 0–10 V signal, calibrate full retraction and full extension, then split the span into 12 equal intervals. You need no signal conditioner and no motor drive to reach this accuracy; both are upgrades you add only if the actuator coasts past its target. This article walks through the wiring, the calibration math, and the decision of when a drive is worth adding.

What the potentiometer tells you #

A feedback actuator carries a three-terminal potentiometer whose wiper is geared to the moving carriage. Powered across its outer leads, it becomes an adjustable voltage divider: the wiper voltage is proportional to position, with effectively continuous resolution. The practical limit is repeat accuracy, which for a potentiometer is typically quoted between 0.1 and 1.0 mm depending on the resistive element. That is far finer than a job described as "13 positions, accuracy not critical" needs, and it is the same 0–10 V position-signal scheme used when controlling hydraulic cylinder position from a 0-10 V analog input. If you have not chosen the actuator itself yet, sizing an electric actuator to replace a pneumatic cylinder covers the load and force side first.

Wiring the pot into the analog input #

Pot lead Function Connect to
Outer lead (one end of the track) Reference low 0 V of the excitation source and the analog input common
Wiper (middle lead) Position signal Analog input channel +
Outer lead (other end of the track) Reference high Stable positive excitation matching the input range

Use the analog card's own excitation or reference output where it has one, or a lightly loaded regulated supply. The reading is ratiometric: whatever voltage sits across the track appears scaled on the wiper, so the excitation must stay inside the input's range. Feeding a channel rated to 10 V from a 24 V rail overranges it, and a 5 V-rated input clips at anything above its own maximum — match the excitation to the card, not the other way round.

Current draw is trivial: a 10 kΩ pot across a 10 V source passes 10 V ÷ 10,000 Ω = 1 mA, so the track never heats appreciably and the divider stays linear.

Run the pot leads as shielded twisted pair, ground the shield at the PLC end only, and keep them routed away from motor leads and drive output cables. This is the same 0–10 V signal discipline any analog position input needs.

Calibrate two points, then compute the 13 targets #

The variable names below are illustrative; use your own tags in your software.

  1. Drive the actuator to full retraction and record the raw analog counts as an integer called RAW_MIN.
  2. Drive it to full extension and record the raw counts as RAW_MAX.
  3. Compute Span = RAW_MAX - RAW_MIN.
  4. For each index i from 0 to 12, compute Target[i] = RAW_MIN + i * Span / 12. Thirteen targets come from twelve equal intervals — that off-by-one is the most common mistake in this setup.
  5. Declare in-position only when the reading stays inside the target plus or minus a deadband of ±20 counts for several consecutive scans, which rejects noise and a moving carriage.

One safety note: calibration drives the carriage over the full stroke unattended. Keep hands, tools and loose clothing clear of the carriage and its pinch points while the calibration cycle runs.

Worked example: 13 positions on a 100 mm stroke with a 14-bit input #

Inputs, all example values for this case:

  • Stroke: 100 mm (a typical mid-size feedback actuator; take the real figure from your actuator's datasheet).
  • Potentiometer: 10 kΩ, spanning the full stroke — confirm on the datasheet that the pot runs end to end with the carriage, since some actuators reserve a margin at each end.
  • Excitation: 10.00 V across the outer leads.
  • Analog input: a 14-bit unipolar channel reporting 0 to 16383 counts over 0–10 V.
  • Measured calibration points: RAW_MIN = 0, RAW_MAX = 16383 (a full-range channel; your two-point calibration substitutes whatever it actually reads).

Rule in words: thirteen targets divide the span into twelve equal intervals, so counts per position equals the span divided by twelve.

Arithmetic:

  • Counts per position: 16383 ÷ 12 = 1365.25, so the targets land at 0, 1365, 2731, and so on up to 16383.
  • Voltage per position: 10.00 V ÷ 12 = 0.833 V.
  • Position per step: 100 mm ÷ 12 = 8.33 mm.
  • Resolution: 100 mm ÷ 16383 counts = 0.0061 mm per count.
  • The ±20-count deadband is therefore ±0.12 mm (20 × 0.0061 mm), roughly 70 times tighter than the 8.33 mm step and on the order of the pot's own 0.1 mm repeat accuracy — the deadband, not the sensor, sets the position window.

Decision for these inputs: 13 positions hold to within a couple of tenths of a millimetre, far beyond what "accuracy not critical" asked for. The build survives a cheaper card too: at 12 bits, 4095 counts ÷ 12 = 341 counts per position, and the same ±20-count deadband becomes ±0.49 mm — still adequate for discrete stations.

No drive, speed zones, or a drive: the decision #

Nothing but discrete outputs. Switch the actuator's motor forward and reverse through relays or an H-bridge and stop inside the deadband. DC actuators decelerate repeatably, and a brief reverse pulse trims the occasional overshoot. Decision: this is the starting point for 13 positions at relaxed accuracy — no conditioner, no drive.

Two or three speed zones. Select fixed speeds with discrete outputs — relay contacts and fixed resistors, or multi-speed inputs on the motor switching gear. Run full speed in the middle of the stroke and a slow zone within one step of the target. Decision: add this when a single-speed stop regularly coasts past the window.

A drive with an analog speed-reference input. The PLC reads the pot and commands the drive, which gives ramped speed under varying load. The drive never reads the potentiometer itself; a speed-reference drive has no feedback channel, so the wiper always lands on the PLC analog input. When that drive is a VFD on an AC motor, how a PLC controls a VFD: five interfaces compared lays out the wiring options. Decision: add a drive last, and only if trim pulses and speed zones do not hold the window.

Keeping the reading stable #

  • Feed the excitation from a stable, lightly loaded source. Because the reading is ratiometric, excitation sag shows up directly as position error.
  • Use shielded twisted pair with the shield grounded at the PLC end only, routed away from motor and drive wiring.
  • Average four to eight samples and require several consecutive in-window scans before declaring in-position. A DC actuator is electrically noisy while running, so judge position after motion stops or inside the slow zone.
  • Verify by hand: with the actuator unpowered at the motor but the pot energized, a multimeter on the wiper should sweep smoothly across the stroke. Jumps or dead spots mean a worn track or a loose wiper, and the pot — not the program — needs replacing.

Questions asked

Can the motor drive read the potentiometer directly?

No. A drive with an analog speed-reference input accepts a command signal on its reference terminals; it has no position feedback channel. The wiper signal must land on the PLC analog input, and the PLC commands the drive from there. Wiring the pot into the drive's reference terminals would command the drive with a voltage that changes as the actuator moves, and the axis would run away.

Do I need a signal conditioner between the potentiometer and the PLC?

Not when the PLC already has a voltage analog input and a suitable low-voltage excitation source, which is the common case. A resistance-input analog module is a second direct route: it sources its own measurement current and reports ohms, which you linearize with the same two-point method. A conditioner earns its place only when your existing input type and the signal genuinely do not match.

How many positions can this arrangement really hold?

Far more than 13 on the input side. The example channel resolves thousands of distinct counts across the stroke, so the analog input is never the limit. The practical ceiling is the potentiometer's repeat accuracy, typically between 0.1 and 1.0 mm depending on the resistive element; on a 100 mm stroke that leaves room for dozens of positions, with 13 comfortably inside the margin.

What if 13 positions is not enough?

Divide the span by more intervals; the arithmetic is identical. The limit is the potentiometer's repeat accuracy — once the step size approaches that value, extra targets become guesses rather than positions. For genuinely fine positioning across many stations, an encoder-feedback actuator or a servo axis is the next hardware step, not a smaller deadband on the pot.

Keep reading

  • Selection guide

    Linear actuator for pipette travel: what decides the choice

    A guided stepper-driven lead-screw axis with its own RS-232 or RS-422 motion controller is the practical choice for a 300 g pipette over about 150 mm of travel. The decision turns on what the 2 mm measures at the pipette tip, the offset moment on the carriage guide, power-off holding on a vertical mount, and a controller that stores programmed positions.

    Linear motion, bearings and guides

  • Selection guide

    Selecting a High-Temperature Linear Actuator for Oven Belt Tracking

    Standard electric linear actuators carry maximum ambient ratings of roughly 60–80 °C, so none of them survives the 250–300 °C inside a conveyor oven. Mount the actuator, its feedback and its drive outside the oven wall and let a heat-resistant mechanical linkage move the belt-tracking roll. Add an insulated, continuously air-purged enclosure only where a stabilized measurement still shows the actuator above its rating.

    Linear motion, bearings and guides

  • Selection guide

    Sizing a Long-Stroke Linear Actuator for a 500 N Push

    Measure force versus position through the seal before choosing hardware, then size from F_required = F_resistance + m_total × a. With 500 N and an 80 kg workpiece the workpiece-only acceleration ceiling is 6.25 m/s². Order an axis rated at least twice the measured requirement — 1000 N against that process force — and let the thrust-speed envelope, the screw-speed limit over the stroke, and the duty cycle pick belt, ball screw or worm drive.

    Linear motion, bearings and guides