Resolver feedback servo selection for small 0.7 kW axes
Short answer
A resolver requirement gates servo selection on feedback hardware, not on power rating. Confirm the exact drive hardware takes the resolver natively, size each 0.7 kW axis from its motion cycle instead of the kilowatt label, then choose between one resolver-capable multi-axis system and separate single-axis drives. An oversized frame is a fallback, not the default.

On this page
- Which servo drives actually take resolver feedback?
- Can you run a 0.7 kW motor on a 3 kW resolver drive?
- How much torque and speed does a 0.7 kW axis actually need?
- Does stepping the supply down to 240 V fix anything?
- How accurately can a resolver place a load through a gearbox?
- Should you buy one multi-axis system or three single-axis drives?
- What must you confirm before ordering?
- Questions asked
A resolver requirement gates servo drive selection on feedback hardware, not on power rating: when the only family with a native resolver input starts at a 3 kW smallest frame, that frame is the wrong answer for a 0.7 kW axis, and a family that fits the power range is useless if its feedback inputs stop at encoders. Work the selection in the order that kills candidates fastest: resolver input on the exact drive hardware, commutation for that motor, drive size against the calculated duty cycle, supply class, resolver accuracy through the gearbox, then the architecture call between one multi-axis system and separate single-axis drives. The worked example below sizes one axis from a 20:1 gearbox and a real motion cycle, and the closing gates are the order sheet.
Which servo drives actually take resolver feedback? #
Only the exact drive hardware can answer this: check the drive's hardware manual for a native resolver input or a documented feedback option card, because a feedback label that appears in configuration software belongs to the software tree, not necessarily to the hardware you picked.
Start in the feedback chapter of the hardware manual, not the family brochure. A resolver is a passive rotary transformer: the drive energizes a rotor winding and reads back sine and cosine signals whose amplitude ratio gives shaft angle, with no electronics mounted in the motor. That is why hot, vibrating and washdown-exposed machines specify resolvers, and why the requirement keeps appearing in new products. No industry standard fixes a resolver interface; the drive and motor manuals do, and they must agree on excitation voltage and frequency, transformation ratio, cable type and length, and pinout as one documented pairing.
The drive also has to close the commutation loop from those signals; position reporting alone is not commutation. Treat a feedback option that appears in configuration software as unconfirmed until the hardware manual for your exact frame lists it, because large servo families carry feedback variants in the software tree that belong to other drives or to option modules the frame cannot accept. Confirm as well that the drive hands position to your controller at the rate the axis needs; that is a separate question from reading the resolver at all.
If you already hold the motor and are choosing its drive, selecting a replacement servo drive for resolver motors walks these checks against an existing motor. If you are still weighing whether to demand a resolver at all, why new servo motors still offer a resolver instead of an encoder covers the trade.
Can you run a 0.7 kW motor on a 3 kW resolver drive? #
Usually not, and the arithmetic says why: a 3 kW, 3000 rpm drive is rated around 9.55 N·m continuous, more than five times the roughly 1.7 N·m this axis needs, and a current loop sized for the big frame may never regulate cleanly at the small motor's standing current.
The comparison that matters is torque and current, not kilowatts. A 3 kW frame rated at 3000 rpm converts to 3000 W ÷ 314.2 rad/s = 9.55 N·m of continuous torque, while the worked axis below asks for a fraction of that. Oversizing at that ratio brings four practical risks: the drive's minimum controllable current can sit above the small motor's standing current, a current loop tuned for a large rotor can hunt on a small one, motor protection modelled for a big frame may not track a small rotor's heating, and the cabinet gives up the space.
None of that is automatically disqualifying, because some families document small-motor operation on larger frames. The test is documentary: the drive maker's data must state a minimum motor current or list your motor, and the tuning range must cover it. If you trial the oversized frame anyway, do it inside the machine's normal guarding with stop functions verified against the machine's risk assessment and IEC 60204-1, not on an open bench. If the documentation cannot confirm the small motor, the frame is the wrong candidate no matter how well the resolver fits.
How much torque and speed does a 0.7 kW axis actually need? #
For the worked axis below, a 20:1 gearbox carrying 30 N·m at the load, the motor sees about 1.7 N·m continuous and 600 rpm; a 0.7 kW, 3000 rpm-class servo clears that duty with margin, and the cycle math, not the kilowatt label, proves it.
Kilowatts alone cannot select a servo; the cycle can. Treat every input as an illustrative example for one axis of a three-axis machine, and replace each with the values from your load study and the datasheet of the exact motor.
Inputs (illustrative example):
- Gearbox ratio N = 20:1, efficiency 0.90
- Load torque at the table: 30 N·m whenever it moves (friction plus process load)
- Load inertia: 0.40 kg·m²
- Cycle: accelerate 0.5 s, run at speed 2.0 s, decelerate 0.5 s, dwell 7.0 s, total 10 s
- Candidate motor, example datasheet values: 0.7 kW, 3000 rpm rated speed, rotor inertia 1.0 × 10⁻⁴ kg·m²
- Inertia added on the motor shaft by coupling and gearbox input: 0.2 × 10⁻⁴ kg·m²
Speed. Load speed 30 rpm = 3.14 rad/s. Motor speed = N × load speed = 20 × 30 rpm = 600 rpm (62.8 rad/s), one-fifth of the rating, so speed is not this axis's constraint.
Torque from the load. T_motor = T_load ÷ (N × efficiency) = 30 ÷ (20 × 0.90) = 1.67 N·m.
Inertia. J_reflected = J_load ÷ N² = 0.40 ÷ 400 = 0.0010 kg·m². Total at the motor = 0.0010 + 0.0001 + 0.00002 = 0.00112 kg·m².
Acceleration. The load reaches 3.14 rad/s in 0.5 s, which is 6.28 rad/s²; at the motor, 20 × 6.28 = 125.7 rad/s². T_accel = 0.00112 × 125.7 = 0.14 N·m, so peak demand = 1.67 + 0.14 = 1.81 N·m.
RMS torque over the cycle. T_rms = √[(1.81² × 0.5 + 1.67² × 2.0 + 1.53² × 0.5 + 0² × 7.0) ÷ 10] = √[(1.638 + 5.578 + 1.170) ÷ 10] = √0.839 = 0.92 N·m.
Checks against the candidate. Rated torque = 700 W ÷ 314.2 rad/s = 2.23 N·m, and the cycle's 0.92 N·m RMS loads that to about 41%. Peak capability is commonly around three times rated, confirm the multiplier in the motor datasheet, so roughly 6.7 N·m stands against a 1.81 N·m demand, about 27%. Inertia ratio = reflected load ÷ rotor inertia = 0.0010 ÷ 0.0001 = 10:1, at the edge of the common rule of thumb of 10:1 or less for a crisply tuned axis, and acceptable for one that creeps and reverses rarely.
Decision for this axis. The demand is about 1.7 N·m and 600 rpm; the 3000 rpm-class candidate clears it with margin, and every remaining question is about the resolver interface, not about power.
Does stepping the supply down to 240 V fix anything? #
A transformer matches voltage, not feedback: stepping 480 V three-phase down to 240 V lets a 240 V-class drive connect to the supply, but it cannot add a resolver input, change a feedback interface or make an incompatible motor-drive combination commutate.
Pick the input class before anything else on the supply side: if resolver-capable families exist in the 480 V class the machine already has, a transformer adds nothing; if the only family that passes the resolver gate is a 230/240 V class, the transformer becomes part of the project. When it is needed, size it from the drives' documented input current, not from the motor ratings: the three motors add to 2.1 kW, but that sum understates the input, because drives draw reactive and switching current whenever they are powered and take acceleration energy from their DC bus capacitors. The working formula is kVA = √3 × line voltage × total documented input current ÷ 1000, and the transformer and drive makers publish the derating rules for inrush and for the harmonic current a drive input feeds back into the transformer.
Settling the supply class also settles braking energy: on slow, frequently reversing axes the drives still absorb regeneration at every deceleration, so confirm how the chosen family disposes of it, a resistor or a regenerating unit, while the order is being assembled.
How accurately can a resolver place a load through a gearbox? #
A resolver's counts are set by the drive's conversion, and a 12-bit conversion giving 4096 counts per motor revolution is a common example, but load accuracy is decided by the gearbox: backlash, lost motion and compliance usually dominate long before the feedback count does.
The two numbers get confused: what the feedback can distinguish and where the load actually stops. The feedback side belongs to the drive's converter. For example, a 12-bit resolver-to-digital conversion yields 4096 counts per motor revolution; converters range from 10-bit to 16-bit and some drives interpolate further, so take the figure from the drive's feedback specification. Through the worked gearbox, 4096 × 20 = 81,920 counts per load revolution, an ideal count size of 360° ÷ 81,920 = 0.0044°, about 16 arc-seconds, finer than any mechanical part of that axis will hold.
On a slow, geared axis the mechanics dominate. Gearbox backlash, lost motion in keys or a belt stage, and compliance under load typically run from a few arc-minutes to tens of arc-minutes depending on gearbox class, with the real figure in the gearbox datasheet, so a direction reversal erases the resolution the reduction multiplied. Specify the accuracy at the load, buy the gearbox backlash rating to meet it, and let the resolver counts do what they are good at on a slow axis: smooth velocity and torque control at low speed.
One resolver advantage survives power-off: shaft angle within a single turn is still valid at the next power-up. Using a resolver as absolute position feedback after power-off explains that property, and it removes a homing move from every restart.
Should you buy one multi-axis system or three single-axis drives? #
Coordination decides: if the three axes must interpolate or gear to each other, one resolver-capable multi-axis system with deterministic cross-axis exchange fits best; if each axis merely indexes to position on its own schedule, three single-axis resolver drives close their own loops and the PLC sequences them.
Write the coordination requirement down before comparing hardware, because it splits the field cleanly:
| Architecture | Fits when | Confirm before ordering |
|---|---|---|
| One resolver-capable multi-axis system | Axes interpolate, gear or cam together, or share one controller | That the family's smallest frame accepts your motor's resolver pairing and current, plus any interface hardware coordination requires |
| Three single-axis resolver drives | Each axis indexes independently and the PLC sequences them | Each drive's resolver input, its controller interface, and how it disposes of braking energy |
| Dedicated motion controller plus resolver drives | Suitable drives exist but the PLC has no native motion commands for them | Ownership of homing, limits, coordinated moves and fault recovery, assigned before logic work starts |
Two notes on the table. Families that reserve coordinated multi-axis control for one drive network and its interface hardware are common, so confirm what that interface adds to the multi-axis path before assuming it is the lighter option. And a general-purpose vector drive on a geared motor is a legitimate answer only when the axis needs speed control with coarse positioning; vector control does not imply a resolver input, so its feedback chapter needs the same reading as a servo's before it displaces one.
If resolver-capable drives exist but your controller cannot command coordinated motion on them, what an external motion controller does for servo drives describes the middle path: keep the drives, change the commander, and assign homing, limits and fault recovery before logic work starts.
What must you confirm before ordering? #
Confirm five gates before you shortlist a family: native resolver input on the exact hardware, commutation for that exact motor combination, current coverage of the calculated torque, a controller interface that reports position at the required rate, and a supply that matches the drive input.
Put the gates in one table and make each one pass or fail:
| Gate | Pass criterion | Where the proof lives |
|---|---|---|
| Resolver input | The exact drive hardware lists native resolver feedback or a documented option card | Drive hardware manual, feedback chapter |
| Commutation | The drive-motor pairing is listed as commutating from the resolver | Drive and motor compatibility data |
| Drive size | Continuous and peak current cover the cycle math with margin | Your sizing sheet against the drive's current ratings |
| Controller path | The drive reports position and accepts commands at the rate the axis needs | Drive interface documentation |
| Supply | Drive input class matches the supply, or a transformer sized from documented input current | Drive input data and the transformer calculation |
The decisions, case by case. Axes that index independently: three single-axis drives with native resolver inputs, each sized by its cycle math and sequenced by the PLC, with the joint between each motor and its gearbox specified too, down to a flexible shaft coupling whose inertia the sizing assumed. Axes that coordinate: the resolver-capable multi-axis platform whose smallest frame matches the motors, or an oversized frame only when the drive maker's small-motor documentation is in hand. A controller that cannot command the chosen drives: add a dedicated motion controller and give it homing, limits and fault recovery. In every case the resolver gate falls first, and power ratings only sort the survivors.
Questions asked
Can a resolver be retrofitted to a servo motor that shipped with an encoder?
Rarely as a field change. The feedback package is built into the motor's mechanical and electrical design, so the documented paths are ordering the motor variant with resolver feedback or using the drive maker's documented feedback conversion, followed by re-establishing commutation. Plan the feedback type during motor selection; retrofitting later usually means more downtime than changing the motor.
What does resolver wiring add compared with an encoder cable?
A resolver needs an excitation supply pair from the drive plus sine and cosine return signals, typically six or more conductors in a twisted, shielded cable, and the drive manual sets maximum length and separation from motor power conductors. Route the resolver cable away from the motor cable and terminate the shield exactly as the drive manual instructs.
Is resolver feedback immune to electrical noise?
No, but it is comparatively tolerant. The useful signal is a low-impedance amplitude ratio between two windings rather than a counted pulse edge, so induced noise must be large to corrupt it, which is why resolvers suit hot, vibrating and electrically noisy cabinets. They still need the shielding, grounding and routing the drive manual specifies, especially near drive output cables and contactor coils.
What should a spare-parts plan record for a resolver servo axis?
Record the resolver pairing in the machine file: the motor's feedback datasheet, the cable drawing, and the drive catalog entries that natively accept that resolver. Those documents let a future buyer match any replacement drive to the existing motor without guesswork, because resolver compatibility is a documented pairing of one drive and one motor, not a family-level promise. Add a copy of the drive manual's feedback chapter to the same file.