When a Servo Lag Excess Hides in Axis Load

Servo and stepper motion Published 8 min read By AutomateDirectUSA engineering team

Short answer

If a servo lag excess alarm survives a new CNC board, new encoders and a complete drive swap, the fault is on the load side of the axis. In this SQT 10 MS case an intermittent hydraulic counterbalance restriction raised the X-axis load; the machine ran clean at 30% rapid and tripped within minutes at higher overrides, with alarm time shrinking as rapid rose. Work the speed-dependence test, then the load checks.

On this page
  1. The signature that separates load from feedback
  2. Why the board and drive swaps came up empty
  3. The check order, cheapest first
  4. Reading time to alarm on an SQT 10 MS at 40 and 80 percent rapid
  5. Inside the counterbalance: the obstruction that hid
  6. Proving the fix, and the decision at each branch
  7. Questions asked

When every electronic part on an axis has been swapped and a servo lag excess alarm still comes back, stop swapping and check the load the axis moves. On a Mazak SQT 10 MS turning center with a T32-3 control, an intermittent X-axis lag excess survived a new CNC board, new ball-screw and motor encoders, a complete three-axis drive unit, fresh parameters and a new battery backup. The fault was hydraulic and mechanical: a nut inside the X-axis counterbalance would occasionally plug the fluid passage, raise the load the servo had to move, and drive the following error past its limit. The machine ran quietly at a low rapid override and tripped within minutes whenever the override went higher, with the interval shrinking as the override rose. Below are the symptom pattern, a check order that finds such faults cheaply, and a worked test that separates load from electronics.

The signature that separates load from feedback #

A lag excess alarm is the servo family's way of saying the measured axis position fell too far behind the commanded position for longer than the control allows. Different controls name the same condition a following error, an excess error or a servo lag alarm; the general lag checks are laid out in what causes a PLC servo axis to lag or stop off position. On this machine the pattern had five parts:

Observation on the SQT 10 MS What it rules in or out
Quiet for months at 30% rapid The axis holds position at low demand; nothing about the electronics is proven either way
Random alarm within minutes above the quiet setting, sooner as rapid rises Time to alarm depends on speed, the classic load-side signature
Same result on different programs Program content is not the trigger
Alarm on X-only and combined X/Z moves The shared element is the X axis, not one move shape
Drive flips several codes for about half a second, resets itself, red hard-stop banner stays until a control reset The drive saw a condition it could clear alone; the stale banner is a display state, not a second fault

Raising the rapid override shortens move times, so the axis must accelerate and decelerate harder on every stroke, and a marginal axis that holds at low override loses its margin when the ramps steepen. That is the same mechanism behind why a servo faults when acceleration ramps increase. The shape is not unique to lathes either: on one reported robot case, the same alarm family needed both an external blockage and a demanding trajectory before it fired. Load plus demand is the recurring pair, and alarm time that falls as speed rises is the tell that separates it from feedback noise, which does not care how fast the axis travels.

Why the board and drive swaps came up empty #

The substitution campaign on this machine covered every electronic layer: CNC board 720, the ball-screw encoders, the motor encoders, the complete three-axis drive unit, parameter changes followed by a restore to factory values, and a new battery backup. Wiring was tested as far as the harness allowed, though no swap campaign proves every conductor and crimp. The symptom never moved.

A lag excess watches a difference: command position minus measured position, compared against an allowance set in the control. Fresh electronics change how accurately the axis is commanded and measured; they cannot change how hard the axis is to move. When command, drive and feedback have all been replaced without touching the symptom, the remaining suspect is the thing none of them touches: the mechanical and hydraulic load. That is the point to stop buying boards and start measuring load.

The check order, cheapest first #

Work the list from the top; each item carries the confirming check that promotes it or clears it.

  1. Compare the X-axis load meter with the machine's own baseline. Run a program that historically ran clean at the quiet override, record the load meter, then step the override up and watch it. The confirming observation is a load reading that climbs with the override instead of holding near its clean-run level. This lathe has no published load acceptance figure, so its own clean-run baseline is the reference, and an elevation above that baseline is the confirmation.
  2. Listen at the ways and the ball screw. Cycle the X axis through its working stroke and listen for grinding, clicking or tight spots; a failing thrust bearing or a dry, binding screw is audible before it shows on any meter. Confirming check: noise that rises with speed.
  3. Free or remove the way cover and dry-cycle the axis. A dragging cover loads the axis exactly like a failing bearing and costs far less to test. Confirming check: the alarm timing unchanged with the cover free, or visible drag on it.
  4. Recheck alignment if the machine has been crashed. A crash can shift the ball screw out of parallel and add load along the whole stroke. Confirming check: binding that appeared after a known crash.
  5. Inspect the hydraulic counterbalance, even after a recent adjustment. An adjustment sets a valve or pressure on the outside; it cannot remove a part moving around inside the cylinder. Confirming check in this case: an intermittent internal restriction found in the counterbalance.
  6. Leave the ball screw and bearings for last. They are the costliest items on the list, and the load meter and noise checks above will already have pointed at them if they are the cause.

One caution before item 5 or any screw work: on a 45-degree slant bed the X axis stores gravitational energy and the counterbalance circuit stores hydraulic pressure. Support the moving mass, relieve the hydraulic circuit per the machine's service manual, and lock the machine out before opening anything; the manual and the shop's risk assessment govern the procedure.

Reading time to alarm on an SQT 10 MS at 40 and 80 percent rapid #

Inputs, with their sources:

  • Machine and control: Mazak SQT 10 MS with a T32-3 control, the machine in this case.
  • Quiet reference: months of alarm-free running at 30% rapid, taken from the case history; rapid is the percent of maximum rapid travel rate.
  • Test settings: 40% and 80% rapid, illustrative settings above the quiet threshold and inside the override range the case exercised. Replace them with your own choices.
  • Times to alarm: illustrative stopwatch values inside the few-minute band the case reports — runs of 4, 4 and 3 min at 40% rapid, and 2, 2 and 2 min at 80% rapid. These stand in for your own timed runs.
  • Held constant: one part program for every run, because the test must isolate speed; the case itself showed the alarm on more than one program.

The rule, in words: in this case the interval to alarm shortened as the override rose, so the working signature is that a load-driven lag excess halves its alarm time when the override doubles. The test compares the ratio of alarm times with the ratio of overrides.

The arithmetic, on the illustrative values:

  • Median time at 40% rapid: the middle run of 4, 4 and 3 min is 4 min. Median at 80% rapid: 2 min.
  • Override ratio: 80% ÷ 40% = 2.0.
  • Time ratio: 4 min ÷ 2 min = 2.0.
  • Constant-product form: 40% × 4 min = 160 percent-minutes, and 80% × 2 min = 160 percent-minutes. The percent-minute product is a diagnostic index, not a physical quantity.

Result: time to alarm halved exactly when the override doubled, and the index held at 160 percent-minutes at both settings. The alarm tracked axis demand, not the program.

Decision: when the time ratio matches the override ratio within the scatter of your own repeat runs, the alarm is load-driven — skip further electronics and start the check order above, load meter first. When alarm time stays flat as the override rises, this signature is absent, and the feedback path deserves another pass before you spend on mechanics.

Inside the counterbalance: the obstruction that hid #

The counterbalance had been adjusted earlier in the hunt and reported fixed, which is why it stayed off the suspect list too long. The confirmed defect was internal: every so often, a nut inside the unit plugged the hole the hydraulic fluid passes through. Because the restriction came and went, the extra load came and went, and that produced the random timing; the servo carried the added load until the following error crossed its limit and the drive flipped its codes.

One clue pointed at the hydraulic side a day before the find: the power unit tripped the thermal overload switch on its hydraulic motor, and it was reset and forgotten. A counterbalance that restricts its assist makes the servo carry the axis weight by itself — the same failure family seen from the motor-temperature side in why a vertical axis servo motor overheats from counterbalance loss. Clear the internal obstruction and the axis load returns to its baseline, which is what the repair must be confirmed against.

Proving the fix, and the decision at each branch #

Verification is the test that found the fault, run in reverse. After the counterbalance repair, rerun the programs that tripped at overrides above the old 30% ceiling: three consecutive clean cycles at each of two overrides, the X-axis load meter tracking its baseline, no code flip and no hard-stop banner. Only then return the machine to its normal rapid.

The closing decision, for each case:

  • Alarm time falls as the override rises and matches the override ratio: the fault is on the load side. Work the check order from the top, and keep the counterbalance on the list even after a recent adjustment, because internal obstructions hide behind fresh settings, as this one did.
  • Alarm time is flat across overrides, or the alarm fires at the quiet override too: the speed signature is absent. Return to the feedback path — encoder cables and connectors, grounding and shielding, the lag allowance setting in the control, and the drive itself — before spending on mechanics.

Questions asked

Why did the fault only appear when the rapid override went up?

Higher rapid does two things at once: the X axis meets the intermittent restriction more often each minute, and each stroke demands harder acceleration, so the servo's margin against the lag limit disappears sooner. That is why the interval to alarm shrank as the override rose, while months passed without a fault at the quiet setting.

Can a reset clear a servo lag excess alarm for good?

No. In this case the drive dropped its codes by itself after about half a second, and the red hard-stop banner stayed until a control reset, but the alarm returned as soon as the override rose. A reset clears a state, not a load; the durable fix was repairing the counterbalance.

What should I record before calling a service engineer about a lag excess alarm?

Log the rapid override, the program number, the time from cycle start to alarm for three runs at each of two overrides, the X-axis load meter readings against the same-program baseline, and any hydraulic-side events such as an overload trip on the hydraulic motor. That record reproduces the speed-dependence test and points the visit at load instead of electronics.

Is running at the reduced override a safe way to keep producing?

Treat it as a temporary workaround, not a fix. The restriction is mechanical and intermittent, so it can worsen without warning. Keep watching the X-axis load meter against its baseline, note any alarm appearing at lower overrides, and schedule the counterbalance inspection rather than postponing it.

Keep reading

  • Troubleshooting

    Diagnosing Servo Axis Position Drift in the Drivetrain

    The drift is lost motion between the motor encoder and the load: the position loop closes at the motor shaft, so the gearbox, coupling, pulleys and belt sit outside it. Split motor-reported position from an independently measured load position at one reference with witness marks on every hub. A one-direction offset that grows for hours while the motor reads on target is index loss — slip or jumped teeth — until the marks prove otherwise.

    Servo and stepper motion

  • Troubleshooting

    Fixing Non-Circular Servo Cuts: Servo Lag Not Encoder Wiring

    No. Connect the motor encoder to the servo drive, not to Mach3: the drive closes the position loop, and Mach3's Encoder/MPG inputs can only read counts, not correct them. Distorted circles come from unequal X and Y servo lag during acceleration and reversal, so fix them with per-axis gain and damping in the drive, then by removing reversal lost motion in the mechanics.

    Servo and stepper motion

  • How-to

    Synchronizing Two Servo Axes on One Heavy Lift

    Yes, two servos can raise one 900 lbf fixture — gear both real axes to one virtual master, trip a cross-axis position fault that halts the master when either side strays, watch the two motor currents separately, and counterbalance each side so the holding brakes stop drifting the level away. Identical independent commands are not synchronization.

    Servo and stepper motion