Servo and stepper motion Published 8 min read By AutomateDirectUSA engineering team

Short answer

A vertical servo axis that drops on E-stop or control-off has no passive holding force: the motor holds only while the drive supplies torque, and no parameter changes that. The fix is a working spring-applied holding brake, a counterbalance or a self-locking mechanism. Block the axis, confirm the brake option from the motor order number, then measure the brake coil voltage in every machine state.

On this page
  1. What holds a vertical axis once torque is gone
  2. Read the symptom before touching anything
  3. Find the fault in order of cost
  4. Brake timing: clamp before the torque leaves
  5. Worked example: the stamping machine axis that drops in every state
  6. Prove the repair with the axis still blocked
  7. Fixes that do not hold
  8. Questions asked

A vertical axis that travels down when you press the E-stop or switch the control off has no passive holding force. A servo motor holds a load only while its drive is pushing current through the windings; the moment torque disappears, gravity has the axis, and no parameter changes that. What keeps a vertical axis in place is one of three things: a working spring-applied holding brake, a counterbalance that carries the weight, or a self-locking mechanism. On a machine that has dropped since commissioning, the usual finding is a brake that was never ordered, never wired, or wired to a supply that never drops out. Diagnose in this order: block the axis, confirm the brake from the motor's order number, then measure the brake coil voltage in each machine state.

What holds a vertical axis once torque is gone #

An E-stop and a control-off both remove the drive's ability to produce torque. Control-off also removes every software function in the machine, which is why a fault present in both states cannot be a program or tuning problem: nothing the control executes survives it. The same physics is why a vertical Z axis back-drives with servo power off — take away the current and the load is free.

Only passive devices hold with no energy available:

  • Spring-applied holding brake. Springs clamp the shaft; energizing a coil lifts them. The coil's release voltage and polarity are specified in the drive user manual and the brake data of the motor catalog — measure them, never assume them. It is a parking brake for standstill — the split between parking and stopping duty is covered in what a servo motor holding brake does and does not do — and using it to stop a moving load every cycle wears the friction surfaces early.
  • Counterbalance. A gas spring, counterweight or cylinder offsets the axis weight so the drive handles only the residual torque; a pneumatic counterbalance for a vertical Z axis is the usual retrofit.
  • Self-locking mechanism. A high-ratio worm stage or a low-lead screw that the load cannot back-drive.

One catalog number matters later: the brake closing time, the delay between removing coil voltage and reaching full holding torque at the shaft. It is listed for each motor size.

Read the symptom before touching anything #

Order the checks by what they cost — decoding an order number costs a catalog page, a timing comparison costs an afternoon. A symptom alone never names the cause; the confirming check does.

What you observe Most likely cause Confirming check
Shaft turns freely by hand with power off No brake fitted, or brake permanently released Order number decoded against the motor catalog, then the hand test
Dropped since commissioning, never once held Brake never wired, or fed from an unswitched supply Coil voltage in all three machine states
Sags a short distance, then holds Brake closes after the torque is gone Brake closing time against the drive's stop sequence
Clicks on power removal, creeps under load Worn friction, or holding torque below load torque Worst-case load torque against the catalog holding torque
Holds all day while enabled, drops only at E-stop Normal servo hold hiding a dead brake path Coil voltage with the drive disabled

Find the fault in order of cost #

  1. Block the axis and lock out. Fit a pin, post or clamp under the moving mass before you open anything. A falling axis of this kind damages mechanical stoppers and anything under it; keep your hands out of its travel.
  2. Decode the motor. Copy the order number from the rating plate and read it against the manufacturer's catalog for that motor family. The brake is an option encoded in the order code, and the same catalog entry gives the brake's holding torque in N·m and its closing time. Never infer a brake from the motor's length or from what the machine was supposed to have.
  3. Hand-test the brake. Power off, try to turn the motor shaft by hand or with a torque wrench. A working brake resists hard; a shaft that spins freely means no brake, a released brake, or a worn one.
  4. Measure the coil in three states. Meter across the brake terminals at the motor connector: axis enabled and released, E-stop pressed, control off. Expect the release voltage while enabled and nothing in the other two states.
  5. Trace any live coil. If the coil still carries voltage with the drive dead, its feed never drops out: welded relay contacts, a brake pair wired straight to the supply, or a jumper left at commissioning. Route the coil through the controlled output — the PLC output or drive brake output that commands the interposing relay — and inspect that relay and its suppression diode while you are there.
  6. If it clamps but creeps. Compare the worst-case static load torque (heaviest tooling, least favorable position) with the holding torque listed for that exact brake. A brake below its load, or one worn past service, is replaced — brake or motor, whichever the motor family allows.
  7. If there is no brake at all. That is a design gap, not a failure. Fit the brake version of the same frame size with its control circuit, add a counterbalance, or add a self-locking device. A vertical axis held by drive torque alone drops every time power is cut, forever.

Brake timing: clamp before the torque leaves #

With a working brake, a short sag can remain when the drive cancels torque before the brake reaches full grip. Two times have to meet: the brake closing time from the catalog, and the delay between the stop command and torque removal in the drive's shutdown logic. The brake command must lead torque removal by at least the closing time.

Drive makers solve this with a controlled stop: the drive keeps holding the load until a configured coasting time elapses or the motor reaches zero speed, and only then lets the brake take over. One major drive maker's vertical-load guidance documents exactly that sequence and recommends a controlled stop instead of an immediate power cut for vertical loads. IEC 60204-1 defines the categories behind it: a category 0 stop removes power at once, a category 1 stop keeps the drive stopping the motor and removes power after it stands still. Whether this machine's E-stop may act as category 1 belongs to its risk assessment — never rewire a safety function to gain a hold.

Control-off cannot be fixed by timing at all. The drive loses its supply completely, so only the passive brake or counterbalance acts, which makes control-off the honest test of the whole design.

Worked example: the stamping machine axis that drops in every state #

The case: a stamping machine marks serial numbers with a vertical servo axis, and the axis descends on E-stop and on control-off. The behavior goes back to commissioning, roughly 2 to 3 years. The readings below are the pattern this fault produces — take your own before condemning anything.

Inputs and where each comes from:

  • Brake release voltage: 24 V DC, and clamped state 0 V at the coil — brake data in the motor catalog and drive user manual for this brake class.
  • Hand test, power off: shaft turns freely — observed on the machine.
  • Meter at the coil reads 24 V in all three states — enabled, E-stop pressed, control off.

The rule in words: a sound brake circuit applies the release voltage only while the drive is enabled and nothing when it is disabled. The difference between the enabled reading and the disabled reading is the circuit's entire useful output.

The arithmetic:

  • Required change across the states: 24 V - 0 V = 24 V.
  • Measured change: 24 V - 24 V = 0 V.

Result: the coil is energized in every state, so the springs never clamp. Combined with the free-by-hand test, the brake is confirmed permanently released — consistent with a feed wired past the controlled output since commissioning.

Decision: with the drive disabled, the coil must read zero. A reading that stays at the release voltage condemns the release path: find the welded relay contact or the pair wired straight to the supply, route the coil through the controlled output, then repeat the three-state measurement before anything else moves.

Prove the repair with the axis still blocked #

  1. Block still fitted: power up, enable the axis, confirm the brake releases — an audible click at the motor, the release voltage at the coil, a free shaft.
  2. Press the E-stop: the coil voltage falls to zero and the shaft cannot be turned by hand. Switch the control off: the shaft stays locked.
  3. Drop test: dial indicator on the axis, hold position, trigger the E-stop, record the displacement. Repeat at the top and bottom of travel and with the heaviest tooling fitted.
  4. The recorded displacement becomes the machine's baseline; anything inside the process tolerance you set passes, and growth over cycles means the brake is wearing.
  5. Run several cycles: no drift, no abnormal brake noise, no heat at the brake cover.

Fixes that do not hold #

  • A parameter. Control-off removes every software function; nothing the program stores can hold the axis then.
  • A jumper across the brake relay to silence nuisance trips. That permanently releases the brake — it manufactures the exact fault in the worked example.
  • A replacement motor of the same frame size without the brake option. Flange and shaft fit; the hold is gone.
  • Dynamic braking or a regen resistor. Both need the drive powered and in control, and both die with the supply.
  • Counting on the drive staying enabled after the E-stop. That is a controlled-stop design decision for the risk assessment, not a wiring shortcut.

Questions asked

Why does the axis hold perfectly all day and drop only when someone presses the E-stop?

While the drive is enabled, the position loop holds the axis with continuous motor torque, so a dead or missing brake stays invisible for years. The E-stop removes that torque and exposes it. That is why the fault looks intermittent even when it has been there since commissioning, and why an axis that misbehaves only at power removal should be tested at the brake coil, not in the program.

Can I keep the drive enabled after the E-stop so it holds the axis instead of fitting a brake?

Only inside a stop design the machine's risk assessment allows. A controlled stop keeps the drive stopping the motor before power is removed, but that decision belongs to the safety design, not to a wiring change at the E-stop button. Even then the drive needs a live supply to hold, so a spring-applied brake remains the backup for a supply failure or a control-off.

The brake clicks when power comes off, so why does the axis still creep down?

A click proves the mechanism moves, not that it grips. Put a dial indicator on the axis with the heaviest tooling fitted, trigger the stop, and record how far it moves. Then compare the worst-case static load torque with the holding torque listed for that exact brake in the motor catalog: a worn friction surface and an undersized brake both pass the click test and fail the load test.

How do I tell from the order number whether my servo motor has a brake?

The brake is an option character in the motor's order code. Take the full order number from the rating plate and read it against the manufacturer's catalog for that motor family; the catalog lists which code includes the brake and gives its holding torque and closing time. Do not judge from the motor's shape or length: a brake adds material at the non-drive end, but only the order code proves the option was bought.

Can dynamic braking or a regen resistor replace a holding brake on a vertical axis?

No. Dynamic braking and regen circuits work only while the drive has power and control, and both disappear with the supply, exactly when a vertical axis needs holding. Only a spring-applied brake, a counterbalance or a self-locking mechanism holds with no energy available, which is why a vertical axis needs one of the three no matter how good the drive's stopping is.

Keep reading

  • Troubleshooting

    Why a Vertical Z Axis Back-Drives With Servo Power Off

    A vertical Z axis that drops with servo power off is back-driving its mechanical drive, not losing a control setting. Find and restore the mechanical holding path — in one retrofit the fault was an extremely loose motor-mount belt tensioner — before fitting a brake or counterbalance. A regeneration resistor is never holding hardware, and tuning fixes powered motion only.

    Servo and stepper motion

  • Comparison

    Servo or Stepper for Fast Start-Stop Feed Rollers

    At 28 in feeds and 100 bags/min, a 2 in roller peaks near 1,337 RPM with about 1,400 rad/s² of angular acceleration; through the 5:3 belt drive the motor sees about 2,230 RPM. That is deep in the torque cliff where a hybrid stepper keeps only a fraction of its low-speed torque and loses steps silently, so this machine takes a servo.

    Servo and stepper motion

  • Explainer

    What an asynchronous servo motor is: slip, torque and drive control

    An asynchronous servo motor is a high-performance squirrel-cage induction motor used as a servo axis: the stator field runs ahead of the rotor, and that slip induces the rotor currents that make torque. A vector-controlled drive with the right induction motor model and shaft feedback regulates speed and position to servo accuracy, without permanent magnets in the rotor.

    Servo and stepper motion