Why a VFD Cannot Run a Synchronous Servo Motor

Motors, gearboxes and drives sizing Published 6 min read By AutomateDirectUSA engineering team

Short answer

A VFD in V/f or scalar mode cannot run a synchronous servo motor because it commands only voltage and frequency and has no rotor position input; torque in a permanent-magnet rotor depends on the torque angle, which collapses past 90 electrical degrees without closed-loop commutation. Wire the motor to a servo drive that reads its encoder instead — for the 1FK7 family, a SINAMICS S120 single-axis configuration with a CU310-2 control unit and a PM240-2 power module.

On this page
  1. What a V/f drive actually controls
  2. What a synchronous servo motor needs from its drive
  3. Where the MicroMaster 420 attempt went wrong
  4. Working the torque angle for the 1FK7022 on a V/f drive
  5. Matching a servo drive to the order number and the feedback
  6. The decision for the test bench
  7. Questions asked

A synchronous servo motor cannot be run by a variable frequency drive operating in V/f or scalar mode, and nothing about the wiring is at fault. Torque in a permanent-magnet rotor exists only while the stator current sits at a controlled angle to the rotor field, and only the motor's encoder can tell a drive where that field points. A VFD never reads that encoder, so it cannot commutate the motor. The 1FK7022-5AK71-1 built into the test unit needs a servo drive matched to the motor's order number and feedback interface; for the 1FK7 family, the documented system is SINAMICS S120, configured single-axis as a CU310-2 control unit with a PM240-2 power module.

What a V/f drive actually controls #

A standard VFD makes one decision: what output frequency to synthesize, and what voltage to pair with it. That pairing rule — V/f control, also called scalar control — was written for the induction motor, whose squirrel-cage rotor builds its own magnetic field from slip and therefore needs no position sensor. In scalar mode there is no input for rotor position at all: the drive regulates frequency and voltage through its current-limit loop and nothing else, the control mode behind current-limit loop response time in V/f scalar control. That assumption is harmless for an induction motor and disqualifying for a permanent-magnet servo motor, which cannot be started across the line and depends on the drive producing the correct output, phase by phase, against a rotor it cannot see.

What a synchronous servo motor needs from its drive #

A 1FK7 motor is a permanent-magnet synchronous machine. Its rotor field comes from magnets fixed to the shaft, so the drive must know the rotor position every electrical cycle and place the stator current at the angle that produces torque. That is commutation, and it closes around measured position from the motor's encoder. The rotating magnets also generate a voltage proportional to speed, so a drive built for this machine takes the back-EMF constant and winding data as entered parameters instead of inferring them from slip. Where the rotor field comes from is exactly what separates the two machine types, and synchronous vs asynchronous servo motors and drive use walks through that split. Control mode and feedback are likewise what decides AC servo motor and VFD compatibility.

Where the MicroMaster 420 attempt went wrong #

Numbers that refuse to add up are the designed-in result of that mismatch, not a wiring fault. At standstill a permanent-magnet rotor generates no back EMF, so the applied V/f voltage meets winding that behaves almost like a short circuit: high current, little of it aligned to make torque. The expected pattern is a drive trip on current, a shaft that shudders without turning, or motion that breaks away and slips poles the moment the load shifts. The confirming check is that the same three power leads run this motor from a servo drive — the connection the VFD was missing is the feedback cable, which a scalar VFD has neither the port nor the control mode to use, and no retuning of V/f curves closes that gap.

Working the torque angle for the 1FK7022 on a V/f drive #

Inputs, and where each comes from:

  • Pull-out torque angle: 90 electrical degrees. This is the documented instability limit for a permanent-magnet servo motor driven without rotor position control — torque angle instability sets in beyond it.
  • Torque law: for a permanent-magnet synchronous machine, torque equals the pull-out torque times the sine of the torque angle, the electrical angle between the stator current and the rotor field. This first-order relation is machine physics, not a rating of this particular motor.
  • Example angles: 30, 90, 120, and 150 electrical degrees. These are illustrative inputs that show the shape of the curve; they are not measurements from the test unit.

The arithmetic, relative to the motor's pull-out torque:

  • sine 30° = 0.50, so torque = 0.50 × pull-out torque
  • sine 90° = 1.00, so torque = pull-out torque
  • sine 120° = 0.87, so torque = 0.87 × pull-out torque, 13 percent below pull-out
  • sine 150° = 0.50, so torque = half pull-out torque
  • sine 180° = 0, so average torque is zero

The same law works in reverse for margin. If the test load takes half the pull-out torque, the torque angle is arcsin(0.50) = 30 electrical degrees, leaving 60 electrical degrees of margin; a load step that doubles the load drives the angle to pull-out.

Result: past the pull-out angle the curve folds back on itself. The further the rotor slips, the less torque the motor makes, so the angle runs away instead of recovering.

Decision: only a drive that measures rotor position can hold the torque angle below 90 electrical degrees. A V/f drive never measures it, so on the MicroMaster this motor sits one load step from pole slip; on a servo drive reading the encoder, it does not.

Matching a servo drive to the order number and the feedback #

Start from the nameplate. 1FK7022-5AK71-1 identifies the motor, and any further characters on the label matter, because members of the family differ in winding, connector, brake, and — the item that decides the electronics — the feedback. Read the encoder type from the motor documentation, then confirm the drive's documentation lists that exact interface. This is the same verification as checking a servo drive supports EnDat 2.1 encoder feedback: a connector that physically fits is not proof the drive can read it. Size the power module on the motor's continuous and peak current from the motor documentation, not on commanded speed, because holding a load, accelerating, and friction all draw current at or near zero speed.

The documented drive system for the 1FK7 family is SINAMICS S120. One motor takes a single-axis configuration, a CU310-2 control unit with a PM240-2 power module; several motors take a CU320-2 with Booksize power modules. A servo drive of this class provides analog inputs for a speed reference and digital inputs for direction and enable, so the bench controls carry over.

The decision for the test bench #

Keep the VFD off this motor and commission a servo drive: the SINAMICS S120 single-axis configuration with the CU310-2 and PM240-2, selected against the full order number and the installed feedback. Wire the potentiometer to the analog input, scaled to a restricted test-speed range; map the two direction switches to digital inputs with a separate enable; and decide in advance what happens when both directions are commanded at once, rejecting the conflict rather than letting an undocumented priority decide movement.

Before first motion, secure the unit's mechanism, because the parts connected to the shaft move as soon as torque arrives. Use the machine's designated stopping and isolation arrangements, and treat the direction switches and a zero speed reference as commands, never as a stop.

Questions asked

Can any VFD run a permanent magnet motor?

Some VFD platforms offer a dedicated permanent-magnet control mode that takes the motor's electrical data and an encoder input. In that mode the drive is performing servo commutation and must be documented for the exact feedback interface fitted to the motor. A VFD limited to V/f or scalar control cannot, because it has no rotor position input at all. Check the drive's control-mode list rather than its power rating before connecting a magnet rotor.

What happens if the motor stays wired to the V/f drive?

One of three outcomes: a current trip at start, because the standstill winding with no back EMF looks almost like a short circuit; a shaft that shudders without turning; or rotation that breaks away and slips poles when the load changes. None of these point to a wiring error, and adjusting V/f curves, ramp times, or boost settings will not remove them — the missing input is rotor position, which that control mode never reads.

Does a slow test speed allow a smaller power module?

No. Motor current follows torque demand, not shaft speed: holding a load, accelerating the mechanism, and fighting friction all draw current at or near zero speed. Size the power module on the motor's continuous and peak current from the motor documentation, whatever speed the potentiometer commands. A module chosen for low speed alone will trip the moment the axis has to hold or accelerate.

Keep reading

  • Explainer

    AC servo motor and VFD compatibility: what decides it

    A general-purpose V/Hz VFD cannot commutate a permanent-magnet AC servo: reported bench runs pushed 10–12 A into a 2 A motor with no usable torque, and a second servo grumbled and stalled. Buy a drive that documents the motor type, its feedback interface and a speed-control firmware variant, or a matched motor–amplifier pair, and commission uncoupled at the lowest command.

    Motors, gearboxes and drives sizing

  • Selection guide

    What Decides a Drive for a Resolver-Feedback AC Servo Motor

    A resolver-feedback AC servo motor needs a drive that reads resolver feedback or runs on a retrofitted encoder with hall commutation, accepts step and direction in position mode, and covers the motor's continuous and peak current at its voltage class. A lower supply class keeps the torque and caps top speed; work the checks in order and the decision follows.

    Motors, gearboxes and drives sizing

  • Selection guide

    Resolver feedback servo selection for small 0.7 kW axes

    A resolver requirement gates servo selection on feedback hardware, not on power rating. Confirm the exact drive hardware takes the resolver natively, size each 0.7 kW axis from its motion cycle instead of the kilowatt label, then choose between one resolver-capable multi-axis system and separate single-axis drives. An oversized frame is a fallback, not the default.

    Motors, gearboxes and drives sizing