Troubleshooting
Why a servo drive alarm returns after you reset it
Short answer
Resetting a servo drive alarm without removing its documented cause just queues the same trip. Record the exact code, match it in the troubleshooting chapter of the manual for the installed drive, then work the checks cheapest first: wiring, supply, parameters, mechanical load, thermal duty. Reset once, with the run command off, and verify the axis completes full production cycles without the code returning.

On this page
The alarm came back because the thing that raised it is still there. A servo drive alarm code is a pointer to a documented cause, not the fault itself, and a reset clears only the indication. It cannot repair a binding axis, a sagging supply, or a duty cycle that runs the motor past its continuous torque. Record the exact code first, match it to its documented cause in the manual for the installed drive, then work the likely causes cheapest first: connections, supply, parameters, mechanical load, thermal duty. Reset once, after the cause is corrected and with the run command off, and judge the repair by one test: the axis completes full production cycles without the code returning.
Record the code before anything clears it #
Read the complete code from the drive's display, including any sub-code or detail line under it. If a controller or HMI is connected, record what it reports as well; the two indications should agree, and a mismatch points at the link between them rather than at the drive. Note where in the cycle the alarm appears: at enable, partway into the move, at decel, on one axis only, after the first cycle or after the fortieth.
Then leave the drive alone. Resetting or cycling power before you have the code can erase the sub-code, which is often the part that separates two causes inside the same alarm family. Some drives also store an alarm history in the display or setup software; pull that history before any reset, because it shows what preceded this occurrence.
Match the code to its documented cause #
The troubleshooting chapter of the drive's manual defines the alarm: it lists each code, the documented cause, and the corrective action the manufacturer wrote for it, grouped into the manual's alarm types such as general, overload and encoder alarms. Treat that entry as the test plan and work its causes in the order it gives; the cheapest-first checks below cover everything the entry leaves open.
Confirm the manual matches the drive installed on the machine. Alarm numbering is not universal across drive families, so the manual for the wrong model sends the diagnosis down the wrong branch. Get the manual from the drive maker or its distributor and match it to the exact model on the drive label.
Work the checks cheapest first #
Order the checks by the time and tools they cost, and confirm each one before moving to the next:
- Connections and cables (minutes). Reseat every connector at the drive: motor power, encoder, control I/O, network. Look for chafed insulation and for cable strained at a moving axis. An encoder alarm is wiring until proven otherwise, and the encoder connection error walkthrough starts that branch at the cable and its shield. Route power wiring separately from encoder and signal cables, as servo amplifier manuals instruct, because coupled noise produces alarms that reset clean and return without pattern. Confirming check: the fault disappears when a connector is reseated or a cable is rerouted, and returns when the original routing is restored.
- The supply (minutes, one multimeter). Measure the drive's input at the drive's own terminals while the axis is moving, not at the cabinet feeder. Compare the reading with the input range documented for that exact drive model. A supply that holds at no load and sags when an axis accelerates produces alarms that look random and reset clean. Decision: a reading below the documented range under load means the supply and its wiring are the repair, not the drive.
- Parameters (minutes, needs the manual). Compare the settings tied to the alarm family, such as overload time, current limit and following-error window, against the manual's documented defaults and against what the axis actually does. A following-error window set tighter than the mechanics can hold trips on every fast move; the error counter overflow checklist starts that branch at torque saturation rather than at the number itself.
- Mechanical load (minutes, power off). With the drive disabled and any vertical load secured, turn the driven shaft by hand through its full travel. Binding, a jammed part, dragging seals or a brake that has not fully released all raise the torque the motor must produce until the overload model trips. Confirming check: an axis that turned freely at commissioning and now needs force to turn has been found.
- Thermal duty (one calculation). Compute RMS torque over the production cycle and compare it with the motor's continuous rating from its datasheet. If the demand exceeds the rating, the overload alarm is arithmetic rather than bad luck; the worked example below shows the calculation.
- Environment (minutes). Check ambient temperature against the range documented in the manual, and look for what changed since commissioning: new vibration, a welder or a large variable frequency drive sharing the supply drop, an enclosure fan that stopped. Confirming check: the alarms started when the environment changed.
A worked example: the overload alarm that returns every cycle #
Symptom: the drive trips its overload alarm partway into the cycle, every cycle, and each reset buys exactly one more cycle.
Example inputs, from an illustrative datasheet (take the real numbers from the datasheet of the exact motor): continuous torque 2.4 N·m, peak torque 7.2 N·m. Illustrative motion: 6.0 N·m during 0.4 s of acceleration, 2.0 N·m during 1.2 s of constant travel, 0 N·m during a 0.4 s dwell, for a 2.0 s cycle.
RMS torque over the cycle:
T_rms = sqrt( (6.0^2 × 0.4 + 2.0^2 × 1.2 + 0^2 × 0.4) / (0.4 + 1.2 + 0.4) ) N·m
= sqrt( (14.4 + 4.8 + 0) / 2.0 ) N·m
= sqrt( 9.6 ) N·m
= 3.10 N·m
The demand is 3.10 N·m against a 2.4 N·m continuous rating: 129%. The 6.0 N·m peak sits inside the 7.2 N·m peak rating, so every individual move is accepted, but the drive's electronic overload model integrates the excess between moves and trips once its documented characteristic curve is crossed. That is why the alarm returns on schedule: this is a duty problem, and no reset turns 3.10 N·m of demand into 2.4 N·m of rating. This is a calculated example for these inputs, not a measured result.
Two levers move that number. Cut the move torque from 6.0 to 4.0 N·m and the RMS becomes sqrt( (4.0^2 × 0.4 + 2.0^2 × 1.2) / 2.0 ) = sqrt( (6.4 + 4.8) / 2.0 ) = sqrt( 5.6 ) = 2.37 N·m, which is 99% of continuous: it passes, with no margin left. Add a 2:1 reducer so the motor produces half the torque, assuming the resulting speed stays within the motor's rated speed, and the RMS becomes sqrt( (3.0^2 × 0.4 + 1.0^2 × 1.2) / 2.0 ) = sqrt( 2.4 ) = 1.55 N·m, 65% of continuous: margin restored. Dwell barely moves it, because stretching the dwell from 0.4 s to 1.6 s still leaves sqrt( 19.2 / 3.2 ) = 2.45 N·m, or 102%.
A standing overload that trips with no motion commanded at all is a different branch; the thermal trip at standstill walkthrough covers that case.
Reset safely, then verify with a full cycle #
After the documented cause is corrected, use the reset method the manual gives for that alarm: keypad, controller command or power cycle, whichever it documents for that code. Before resetting, satisfy the condition servo amplifier manuals state for alarm reset: make sure the run signal is off, so the axis cannot be commanded to move the instant the alarm releases. On a vertical axis, secure the load first, because with servo power off the axis is free to back-drive; the vertical axis back-drive article shows what the load does in that state.
Then verify the way the fault will test you: run full production cycles at production speed and duty until the motor reaches its normal running temperature. For a small servo motor that takes tens of minutes, and a housing thermometer turns the wait into a check rather than a guess. One clean move proves nothing to a duty alarm.
If the code returns, capture it again and restart from its manual entry instead of resetting again, because every reset-and-run round re-exposes the drive and motor to the condition that raised the alarm. If two identical drives on similar branches behave differently, the fault localization article settles whether the problem follows the drive or the branch.
The decision for each pattern #
| Pattern when the alarm returns | Most likely cause | Confirming check | Decision |
|---|---|---|---|
| Same point in every cycle | Duty or mechanical load above the continuous rating | RMS torque versus the datasheet rating | Cut acceleration, add a reduction stage, or resize using the four checks in the drive-to-motor matching guide |
| The instant the drive enables | Setup: parameter, phasing or feedback wiring | The code's manual entry, tested at enable with no motion commanded | Correct the setting or wiring the code names before the next reset |
| Random points in the cycle | Connections or coupled electrical noise | Reseat and reroute; the alarm follows the connector or cable path | Repair the wiring path and keep power lines separated from signal lines |
| Only mid-move at full speed | Mechanics or feedback under load | Manual jog at low speed against a loaded full-speed cycle | Work the code's mechanical and feedback checks with the machine loaded |
A reset is the last step of a repair, not the repair. If the axis holds through production duty and the code stays out, the documented cause was found and fixed. If the code comes back, the cause is still there, and the code, not the reset button, is the diagnostic.
Questions asked
Can I just power-cycle the drive to clear the alarm?
Power cycling is one documented reset method on many drives, and it clears the indication like any other reset, but it does not touch the cause. If the code is back at the same point in the next cycle, the cause is still active. Repeated power cycles on an overload alarm keep stressing the motor as well. Correct the documented cause first, then use whichever reset method the manual for your exact drive specifies.
Why does the drive show a different alarm after each reset?
Successive codes usually mean one of two things: the protection is walking up a chain, as when an overload warning becomes an overload trip and then a drive fault, or one root cause raises different alarms depending on where in the cycle it bites. Treat the first code in the sequence as the lead, work its manual entry, and read the later codes as symptoms of the same fault.
Where do I find the alarm code table for a drive with no printed manual?
From the drive maker or its distributor. Current manuals, including the troubleshooting chapter with the alarm table, are published for every current drive family, and most manufacturers keep manuals for discontinued models available too. Match the manual to the exact model printed on the drive label, because the same code number can carry a different meaning in a different drive family.
Is it safe to keep resetting an overload alarm to finish a run?
No. An overload alarm means current above the motor's continuous rating is flowing, and the electronic overload model trips to keep the windings from overheating. Every reset-and-run round re-exposes the windings to that current. Cut the duty with lower acceleration or longer dwells, add a reduction stage, or fit a drive and motor sized for the cycle, and treat the alarm as that sizing decision rather than as a nuisance.